B4: Timer Function - YASKAWA U1000 Series Technical Manual

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

 b4: Timer Function
The timer function is independent of drive operation and can be used to delay the switching of a digital output triggered
by a digital input signal. An on-delay and off-delay can be separately set. The delay timer can help to get rid of chattering
switch noise from sensors.
To enable the timer function, a multi-function input must be set to "Timer function input" (H1-=18) and a
multi-function output must be set to "Timer output" (H2-=12). Only one timer can be used.
b4-01/b4-02: Timer Function On-Delay, Off-Delay Time
b4-01 sets the on-delay time for switching the timer output. b4-02 sets the off-delay time for switching the timer output.
No.
b4-01
b4-02
Timer Function Operation
When the timer function input closes for longer than the value set in b4-01, the timer output switches on. When the timer
function input is open for longer than the value set in b4-02, the timer output function switches off.
demonstrates the timer function operation.
Figure 5.23
Multi-function Contact
Input: Timer Function
Multi-function Contact
Output: Timer Function
b4-03 to b4-08: H2- ON-Delay and OFF-Delay Time
Sets the length of the delay time for contact outputs to open or close for the related functions set in H2-.
No.
b4-03
b4-04
b4-05
b4-06
b4-07
b4-08
Internal data of H2-01
Multi-Function Digital
Outputs of H2-01
Note: Even if the length of the off-delay time and on-delay time for multi-function digital outputs are each less than 100 ms, the
multi-function digital output closes for at least 100 ms.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Name
Timer Function On-Delay Time
Timer Function Off-Delay Time
ON
ON
b4-01
b4-02
Figure 5.23 Timer Operation
Name
H2-01 ON Delay Time
H2-01 OFF Delay Time
H2-02 ON Delay Time
H2-02 OFF Delay Time
H2-03 ON Delay Time
H2-03 OFF Delay Time
ON
ON
b4-04
b4-03
Time period that the multi-function
digital output is closed ≥ 100 ms
Setting Range
0.0 to 3000.0 s
0.0 to 3000.0 s
ON
ON
b4-01
b4-02
Setting Range
0 to 65000 ms
0 to 65000 ms
0 to 65000 ms
0 to 65000 ms
0 to 65000 ms
0 to 65000 ms
ON
ON
b4-03
b4-04
Time period that the multi-function
digital output is closed < 100 ms
Time period that the multi-function
digital output is closed = 100 ms
5.2 b: Application
Default
0.0 s
0.0 s
Figure 5.23
On (Closed)
Off (Open)
On (Closed)
common_TMonly
Off (Open)
Default
0 ms
0 ms
0 ms
0 ms
0 ms
0 ms
On (Closed)
Off (Open)
On (Closed)
Off (Open)
common_
163
5

Advertisement

Table of Contents
loading