A.2 Three-Phase 200 V Class Drives - YASKAWA U1000 Series Technical Manual

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

A.2 Three-Phase 200 V Class Drives

Item
CIMR-U2
Input Current (A)
<1>
Rated Input Capacity (kVA)
Input/
Rated Output Current (A)
Output
Rating
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Rated Voltage Rated Frequency
Allowable Voltage Fluctuation
Power
Supply
Allowable Frequency Fluctuation
Allowable Phase Power Supply Voltage Unbalance
Harmonic Current Harmonic Distortion
Input Power Factor
<5>
<1> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<2> Rated input capacity is calculated with a power line voltage of 240 V  1.1.
<3> The rated output current of the drive output amps should be equal to or greater than the motor rated current.
<4> Carrier frequency is set to 4 kHz. Current derating is required in order to raise the carrier frequency.
<5> If one of the following specifications are needed, the maximum output voltage will be the equivalent to the input voltage  0.87.
 Harmonic current distortion of 5% or less
 Harmonic suppression guidelines compliance
 Input power factor of 0.98 or more
<6> User-adjustable
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Table A.2 Power Ratings (Three-Phase 200 V Class)
0028
HD Rating
20
ND Rating
25
HD Rating
9
<2>
ND Rating
12
HD Rating
22
<3> <4>
ND Rating
28
<5>
A.2 Three-Phase 200 V Class Drives
Specification
0042
0054
0068
0081
25
38
49
62
38
49
62
74
12
17
22
28
17
22
28
34
28
42
54
68
42
54
68
81
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Proportional to input voltage
400 Hz
Three-phase 200 to 240 Vac 50/60 Hz
-15 to 10%
3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
2% or less
5% or less (IEEE519 compliant)
0.98% or more (During rated operation)
0104
0130
0154
0192
74
95
118
140
95
118
140
175
34
43
54
64
43
54
64
80
81
104
130
154
104
130
154
192
<5>
<6>
0248
175
226
80
103
192
248