H: Multi-Function Terminals - YASKAWA U1000 Series Technical Manual

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

B.3 Parameter Table
 H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
H1: Multi-Function Digital Inputs
No.(Addr.)
Name
H1-01
Multi-Function Digital Input
(438H)
Terminal S1 Function Selection
H1-02
Multi-Function Digital Input
(439H)
Terminal S2 Function Selection
H1-03
Multi-Function Digital Input
(400H)
Terminal S3 Function Selection
H1-04
Multi-Function Digital Input
(401H)
Terminal S4 Function Selection
H1-05
Multi-Function Digital Input
(402H)
Terminal S5 Function Selection
H1-06
Multi-Function Digital Input
(403H)
Terminal S6 Function Selection
H1-07
Multi-Function Digital Input
(404H)
Terminal S7 Function Selection
H1-08
Multi-Function Digital Input
(405H)
Terminal S8 Function Selection
<31> Value in parenthesis is the default setting when a 3-wire initialization is performed (A1-03 = 3330).
H1-
Function
Setting
0
3-wire Sequence
1
LOCAL/REMOTE Selection
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (oH2)
C
Analog Terminal Input Selection
432
All Modes
Assigns a function to the multi-function digital inputs.
Refer to
H1 Multi-Function Digital Input Selections on page 432
values.
Note: Unused terminals should be set to F.
H1 Multi-Function Digital Input Selections
All Modes
Closed: Reverse rotation (only if the drive is set up for 3-wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop command.
All Modes
Open: REMOTE (parameter settings determine the source of the frequency Reference 1 or 2 (b1-01, b1-02 or
b1-15, b1-16)
Closed: LOCAL, Frequency reference and Run command are input from the digital operator.
All Modes
Open: Run command and frequency reference source 1 (determined by b1-01 and b1-02)
Closed: Run command and frequency reference source 2 (determined by b1-15 and b1-16)
All Modes
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those
terminals will create a multi-step speed sequence using the frequency references set in d1-01 through d1-08.
All Modes
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference sources.
All Modes
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set in C1-03, C1-04).
All Modes
Closed: No drive output
All Modes
Open: No drive output
All Modes
Open: Accel/decel is not held
Closed: The drive pauses during acceleration or deceleration and maintains the output frequency.
All Modes
Closed: Closes when an oH2 alarm occurs
All Modes
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
Description
for a description of setting
Description
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Setting
Page
Default: 40 (F)
<31>
Min: 1
227
Max: 9F
Default: 41 (F)
<31>
Min: 1
227
Max: 9F
Default: 24
Min: 0
227
Max: 9F
Default: 14
Min: 0
227
Max: 9F
Default: 3 (0)
<31>
Min: 0
227
Max: 9F
Default: 4 (3)
<31>
Min: 0
227
Max: 9F
Default: 6 (4)
<31>
Min: 0
227
Max: 9F
Default: 8
Min: 0
227
Max: 9F
Page
common_
TMonly
227
common_
TMonly
228
common_
TMonly
228
228
common_
TMonly
228
228
common_
TMonly
229
common_
TMonly
229
common_
TMonly
229
common_
TMonly
229
common_
TMonly
229
common_
TMonly
229
common_
TMonly
229