3.12 MEMOBUS/Modbus Termination

3.12 MEMOBUS/Modbus Termination
This drive is equipped with a built in termination resistor for the RS-422/RS-485 communication port. DIP switch S2
enables or disabled the termination resistor as shown in
Table
3.20. The OFF position is the default. The termination
resistor should be placed to the ON position when the drive is the last in a series of slave drives. Refer to
Switches and
Jumpers on the Terminal Board on page 80
for locating switch S2.
Table 3.20 MEMOBUS/Modbus Switch Settings
S2 Position
Description
ON
Internal termination resistor ON
OFF
Internal termination resistor OFF (default setting)
Note: Refer to
MEMOBUS/Modbus Communications on page 487
for details on MEMOBUS/Modbus.