B: Application - YASKAWA U1000 Series Technical Manual

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
No.(Addr.)
Name
b1-01
Frequency Reference Selection 1
(180H)
b1-02
Run Command Selection 1
(181H)
b1-03
Stopping Method Selection
(182H)
b1-04
Reverse Operation Selection
(183H)
b1-05
Action Selection below Minimum
(184H)
Output Frequency
b1-06
Digital Input Reading
(185H)
b1-07
LOCAL/REMOTE Run Selection
(186H)
b1-08
Run Command Selection while in
(187H)
Programming Mode
b1-14
Phase Order Selection
(1C3H)
b1-15
Frequency Reference Selection 2
(1C4H)
b1-16
Run Command Selection 2
(1C5H)
b1-17
Run Command at Power Up
(1C6H)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
All Modes
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse train input (terminal RP)
All Modes
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
All Modes
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
9: Simple Positioning
All Modes
0: Reverse enabled.
1: Reverse disabled.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Operates according to frequency reference (E1-09 is disabled).
1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).
All Modes
0: Input status is read once and processed immediately (for quick response)
1: Input is read twice and processed only if the status is the same in both readings (robust
against noisy signals)
All Modes
0: An external Run command has to be cycled at the new source to be activated.
1: An external Run command at new source is accepted immediately.
All Modes
0: Run command is not accepted while in the Programming Mode.
1: Run command is accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Standard
1: Switch phase order (reverses the direction of the motor)
All Modes
Enabled when an input terminal set for "External reference" (H1- = 2) closes.
0: Digital operator
1: Terminals (analog input terminals)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input
All Modes
Enabled when a terminal set for "External reference" (H1- = 2) closes.
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
All Modes
0: Disregarded. A new Run command needs to be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command is already enabled.
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
B.3 Parameter Table
Setting
Page
common_
TMonly
Default: 1
Min: 0
Max: 4
common_
TMonly
Default: 1
Min: 0
Max: 3
common_
TMonly
Default: 0
Min: 0
Max: 9
<11>
common_
Default: 0
TMonly
Min: 0
Max: 1
common_
TMonly
Default: 0
Min: 0
Max: 3
common_
TMonly
Default: 1
Min: 0
Max: 1
common_
Default: 0
TMonly
Min: 0
Max: 1
common_
TMonly
Default: 0
Min: 0
Max: 2
common_
Default: 0
TMonly
Min: 0
Max: 1
common_
TMonly
Default: 0
Min: 0
Max: 4
common_
TMonly
Default: 0
Min: 0
Max: 3
common_
Default: 0
TMonly
Min: 0
Max: 1
144
145
146
149
150
151
151
152
152
152
152
152
B