4.4

Start-Up Flowcharts

The flowcharts in this section summarize basic steps required to start the drive. Use the flowcharts to determine the most
appropriate start-up method for a given application. The charts are intended as a quick reference to help familiarize the
user with start-up procedures.
Flowchart
Subchart
A
A-1
A-2
A-3
 Flowchart A: Basic Start-up and Motor Tuning
Flowchart A in
Figure 4.8
application. Use drive default parameter settings in simple applications that do not require high precision.
Figure 4.7
Note: 1. When the motor cable length has changed for more than 50 m after Auto-Tuning has been performed (e.g., after the drive has been set
up and then later installed in a different location), execute Stationary Auto-Tuning for resistance between motor lines once the drive
is installed in its final installation location.
2. Auto-Tuning should be performed again after installing an AC reactor or other such components to the output side of the drive.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Basic startup procedure and motor tuning
Simple motor setup using V/f mode
High-performance operation using Open Loop Vector (OLV) or Closed Loop Vector (CLV) motor control
Setting up the drive to run a permanent magnet (PM) motor
describes a basic start-up sequence. This sequence varies slightly depending on the
Install and wire the drive as explained in Chapters 1, 2, and 3
Apply main power on to the drive
Adhere to safety messages concerning application of power
Application Preset
A1-06 used ?
Set the control mode in parameter A1-02.
Set the basic parameters
C6-01 for heavy/normal duty mode selection
b1-01/02 for frequency reference and run command source selection
H1-
, H2-
, H3-
, H4-
, H6-
d1-
for multi-speed references if used
C1-
and C2-
for accel./decel. and S-curve time settings
Control Mode
0: V/f
1: V/f w/PG
To
Flowchart A-1
Flowchart A-2
Fine tune parameters. Adjust application settings (PID, ...) if necessary.
Check the machine operation and verify parameter settings.
Drive is ready to run the application.
Figure 4.8 Basic Start-up
Objective
START
YES
NO
for I/O terminal setting
A1-02 =
2: OLV
3: CLV
To
To
Flowchart A-3
From Flowchart A-1, A-2, or A-3
4.4 Start-Up Flowcharts
Refer to
Application
Selection section
common_TMo
nly
5: OLV/PM
6: AOLV/PM
7: CLV/PM
Page
105
106
107
108
4
105