 H3: Multi-Function Analog Inputs
The drive is equipped with three multi-function analog input terminals: A1, A2, and A3. Refer to
of the functions that can be set to these terminals.
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No.
H3-01
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and
bias settings will be simply read as 0%.
Setting 1: -10 to 10 Vdc
The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.
H3-02: Terminal A1 Function Selection
Determines the function assigned to analog input terminal A1.
on page 250
for instructions on how to adjust the signal level.
No.
H3-02
H3-03, H3-04: Terminal A1 Gain and Bias Settings
Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1 (bias).
Both can be used to adjust the characteristics of the analog input signal to terminal A1.
No.
H3-03
H3-04
Setting Examples
• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):
An input 10 Vdc will be equivalent to a 200% frequency reference and 5 Vdc will be equivalent to a 100% frequency
reference. Since the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will
be equal to E1-04 above 5 Vdc.
Figure 5.79
Figure 5.79 Frequency Reference Setting by Analog Input with Increased Gain
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Name
Terminal A1 Signal Level Selection
Name
Terminal A1 Function Selection
Name
Terminal A1 Gain Setting
Terminal A1 Bias Setting
H3-01 = 0
Gain = 200 %
Frequency
reference
100 %
E1-04
Bias = 0 %
0 V
5 V
Refer to Multi-Function Analog Input Terminal Settings
H3-01 = 1
Gain = 200 %
100%
E1-04
-10 V
-5 V
10 V
5.7 H: Terminal Functions
Table 5.41
Setting Range
0, 1
Setting Range
0 to 32
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
common_
TMonly
5 V
0 V
10 V
-100%
E1-04
Gain = -200 %
for a listing
Default
0
Default
0
Default
100.0%
0.0%
5
247