Wiring The Control Circuit Terminal - YASKAWA U1000 Series Technical Manual

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

3.9 Control Circuit Wiring
Wire Size
Select appropriate wire type and gauges from
wire ends. Refer to
Ferrule-Type Wire Terminals on page 78
Terminal
S1-S8, SC, SP, SN, RP, +V, -V, A1, A2,
A3, AC, M1-M6, MA, MB, MC, MP,
AM, FM, AC, S+, S-, R+, R-, IG, HC,
H1, H2, DM+, DM-
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire
ends with insulated sleeves before connecting to the drive. Refer to
Figure 3.27
Size mm
2
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
 Wiring the Control Circuit Terminal
This section describes the proper procedures and preparations for wiring the control terminals.
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could
result in death or serious injury.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, p1, n1) and other
high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Separate wiring for output terminals MA, MB, MC, M1, and M2 to M6 from wiring to other control circuit lines. Improper wiring
practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral
devices could result in drive performance degradation due to improper power supply.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices
could result in drive or equipment malfunction due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive
or equipment malfunction or nuisance trips.
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer to
Figure 3.28
and
Figure 3.29
Wire Size on page
78.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or
equipment malfunction due to electrical interference.
78
Table
3.10. For simpler and more reliable wiring, use crimp ferrules on the
Table 3.10 Wire Gauges
Bare Wire Terminal
Recomm. Gauge
Applicable Gauge
mm
2
(AWG)
mm
Stranded wire:
0.75
0.2 to 1.0 (24 to 16)
(18)
Solid wire:
0.2 to 1.5 (24 to 16)
Figure 3.27 Ferrule Dimensions
Table 3.11 Ferrule Terminal Types and Sizes
Type
AI 0.25-8YE
AI 0.34-8TQ
AI 0.5-8WH or
AI 0.5-8OG
for details. Prepare the ends of the control circuit wiring as shown in
for ferrule terminal types and sizes.
Ferrule-Type Terminal
Recomm. Gauge
2
(AWG)
mm
2
(AWG)
0.5
(20)
Table 3.11
YEG
d1
d2
L (mm)
d1 (mm)
12.5
0.8
10.5
0.8
14
1.1
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Applicable Gauge
mm
2
(AWG)
0.25 to 0.5
(24 to 20)
for dimensions.
d2 (mm)
1.8
1.8
PHOENIX CONTACT
2.5
Figure
Wire Type
Shielded line, etc.
Manufacturer
3.30. Refer to