6. Mounting system assembly
6a. Check positions of the mountings
Information
U
18375d_52
Information
Mountings are pre-assembled, dependent on the configuration.
Check positions of the pre-assembled mountings ( tables) and correct,
if required ( section 5b).
Mounting 7 for CPX-modules (metal)
Without system feed to module 1
Number of modules
Mounting to the modules
1
−
1 ... 2
3 ... 4
•
•
5 ... 6
•
7 ... 8
9 ... 10
•
With system feed to module 1
Number of modules
Mounting to the modules
2
1 ... 2
−
•
3 ... 5
•
6 ... 8
9 ... 10
•
With system feed to module 1 and module 2
Number of modules
Mounting to the modules
3
−
1 ... 3
•
3 ... 6
•
7 ... 8
9 ... 10
•
If mounting of an attachment 7 is prevented, through an existing system
feed, for example:
Mount attachment 7 to the left or right of the system feed.
Check:
Maximum 3 CPX-modules between 2 mountings 7.
6
Counting direction of the mod-
ules:
CPX (metal):
– from end plate (U).
4
5
8
•
•
•
•
5
8
•
•
•
5
8
•
•
•
6b. Assemble mountings
Mounting 7 to CPX-modules (metal)
1.5 Nm ± 10 %
18373d_50
6c. Mount CPX-terminal to the mounting system
Note
Material damage due to incorrect assembly.
Select screws and slot nuts suitable for the installation situation.
D
Y
7
P
F
18373d_51
Mounting point
Screw size
(D)
M6
(P)
M6
(F)
M6
(H)
M6
Place mounting 7 on the
module (C).
Tighten screws 8. If you
screw it in again, use the
O
threads already present.
7
Observe tightening torques.
8
F
H
H
Number
1x
1x every 7
2x
2x