E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Warnings, cautions and notes As used in this publication Warning notices are used in this publication to Caution notices are used for situations emphasize that hazardous voltages, currents, or...
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Introduction —...
Page 6
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — General description – arc-resistant General description –...
Page 7
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 8
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Bus splicing steps for 2500A without fans, 3 pieces/phase of splices 3000A, and 3200A main bus...
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Installation Note: Before any installation work is begun, consult all drawings, as well as all applicable contract 1.
Page 11
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Indoor enclosures Note: Elevation and Mounting...
Page 12
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Indoor enclosures Elevation and mounting Optional zone 30-inch deep sections 2500A without fans, splice bolt acces...
Page 13
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 14
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — (arc-resistant). bottom conduit entrance details for standard 20-inch deep section, bus upper position.
Page 15
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 16
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Positioning and joining sections For Type 12 and arc-resistant enclosure, see Figure If groups of sections are to be joined together in a 10B for proper gasket in between the section splits.
Page 17
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 18
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Exhaust fan installation for NEMA 1 enclosure If, upon delivery, it is found that standard rear top section covers are in place on the section requiring Exhaust fan for...
Page 19
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 20
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Wiring NEMA type A motor control centers Align the conduit linearly directly over or as close as possible to the supports.
Page 21
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 22
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Shown in Figure 18 there is no restrictions in this setup as the customer can use the hatched area of Plenum-less arc- resistant equipment.
Page 23
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 24
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Wiring between sections Terminal blocks Figure 23A shows the dimensions of side cutouts in The terminal blocks are mounted on a metal rail Side cutout dimensions...
Page 25
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 26
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Removal of draw-out motor control Operating handles, door interlocks and center unit padlocking provisions...
Page 27
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
Page 28
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Pilot bracket and door The pilot device door can be removed by lifting Grasp the center of the door...
Page 29
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L —...
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Operation Preparing for initial operation 7.
Page 31
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L 15.
Page 32
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Door closing procedure of pilot device bracket, extension bubble door for some GP/FP drives E9000 MCC units Door, pilot device bracket and extension bubble...
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Maintenance Equipment maintenance 11.
Page 34
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R — Control power fusing Control fuses are front accessible except in the Fuse location 6-inch compact starter.
Page 35
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Replacing a control power transformer GEH-5198 –...
Page 36
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Spectra circuit breakers 6. Power supply characteristics: DET-244 –...
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Overload heaters Heaters for ther-mag circuit breaker controllers Size 0 and 1 (Standard and Ambient Comp.)
Page 38
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Size 3 (Standard and Ambient Comp.) Size 5 (Standard and Ambient Comp.) Motor Full- Heater...
Page 39
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Size 0 and 1 (Standard) Size 0 and 1 (Ambient Comp.) Mag-Break Trip...
Page 40
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Size 2 (Standard) Size 3 (Standard and Ambient Comp.) Motor Mag-Break Trip Motor...
Page 41
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Size 4 (Ambient Comp.) Size 0 and 1 (Standard) Mag-Break Trip...
Page 42
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Size 0 and 1 (Ambient Comp.) Size 2 (Standard) Motor Full- Mag-Break...
Page 43
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Size 3 (Standard and Ambient Comp.) Size 4 (Ambient Comp.) Mag-Break...
Page 44
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Size 4 (Ambient Comp.) Size 6 – 600:5 CT (Standard and Ambient Comp.) Motor Full- Mag-Break Trip Motor Full-...
Page 45
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Maximum Fuse and Short-Circuit Rating Size 1 (Standard and Ambient Comp.) Motor Full- Load...
Page 46
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Size 3 (Standard) Size 1 (Standard and Ambient Comp.) Motor Full- Heater Maximum...
Page 47
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L Size 5 –...
Page 48
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R Electronic overload for circuit breaker and Catalog numbers of electronic overloads fused controllers for various sizes of NEMA starters and...
Page 49
I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L AF-600 FP / AF-650 GP Drives E9000 Panel mount use with RTXP base adapter Cat.
Page 50
E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R...
Page 52
ABB Inc. 305 Gregson Drive Cary, NC 27511 abb.com/contacts abb.com/lowvoltage GE is a trademark of GE. Manufactured by ABB Inc. under license from General Electric Company. — The information contained in this document is for general information purposes only. While ABB strives to keep...