Introduction
1.6.2.

Conditions of utilization for UL permission

16
UL certification
conform to UL:
Certified
The UL certification is documented by a "UL" logo on the
device (type specification plate)
Conditions of utilization
The devices are only to be installed in a degree of contamination 2 environment
!
(maximum).
The devices must be appropriately protected (e.g. by a switching cabinet).
!
The terminals are suitable for field wiring.
!
Tightening torque of the field wiring terminals (green Phoenix plugs)
!
C3SxxxV2
!
C3SxxxV4 exept C3S300V4
!
C3S300V4
!
Temperature rating of field installed conductors shall be at least 60°C Use
!
copper conductors only
Please use the cables described in the accessories chapter ( see on page 105)
they do have a temperature rating of at least 60°C.
Maximum ambient temperature: 45°C.
!
Suitable for use on a circuit capable of delivering not more than 500 rms
!
symmetrical amperes, 400 volts maximum.
ATTENTION
Danger of electric shock.
Discharge time of the bus capacitator is 5 minutes.
The drive provides internal motor overload protection.
!
This must be set so that 200% of the nominal motor current are not exceeded.
Cable cross-sections
!
Mains input: corresponding to the recommended fuses (see on page 140)
!
Motor cable: ( see on page 121) corresponding to the nominal output
!
currents (see on page 140)
Maximum cross-section limited by the terminals mm
!
C3SxxxV2
!
C3SxxxV4 exept C3S300V4
!
C3S300V4
!
Circuit protection
!
In addition to the branch circuit protection, the devices have to be protected with
the supplementary protector S 261 L, manufactured by ABB.
C3S025V2: ABB, nom 400V 10A, 6kA
!
C3S063V2: ABB, nom 400V, 16A, 6kA
!
C3S038V4: ABB, nominal 400V, 10A, 6kA
!
C3S075V4: ABB, nominal 400V, 16A, 6kA
!
C3S150V4: ABB, nominal 400V, 20A, 6kA
!
C3S300V4: ABB, nominal 400V, 25A, 6kA
!
C3S300V4: ABB, nominal 400V, 25A, 6kA
!
I11 T11 192-120101 N6 - March 2004
according to UL508C
!
E-File_No.: E235 342
!
"UL" logo
0.57-0.79Nm
0.57-0.79Nm
1.25-1.7Nm
2
/ AWG
2.5mm
AWG 12
2
4.0mm
2
AWG 10
6.0mm
AWG 7
2
5 - 7Lb.in
5 - 7Lb.in
11 - 15Lb.in