Technical Data - Siemens Simovert 6SE70 Series Operating Instructions Manual

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
09.02
14

Technical Data

In the event of conditions of use other than those listed in this chapter, please contact your local Siemens
branch or national subsidiary.
Coolant temperature
Storage temperature
Transport temperature
Environmental class
Soiling
Overvoltage category (power section)
Overvoltage resistance class
(with converter connected)
Type of protection
Size C:
− Standard
Size E:
− Standard
− Option
Size H + K:
− Standard
Interference immunity
Mechanical strength
− stationary use
− during transport
The units can also be operated in load class II. The permissible values must be taken from the following tables.
I
(A)
Load class ΙΙ
136%
100%
91%
60s
Figure 14.1
Power output according to load class II
Siemens AG
6SE7087 6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
3K3
2
III
1
IP20
IP00
IP20
IP00
Frequency range
Hz
10 to 58
more than 58 to 500
Load class Ι
240s
t/(s)
Buy Siemens PLC HMI Drives at AoteWell.com
0 °C to +40 °C
− 25 °C to +70 °C
− 25 °C to +70 °C
DIN IEC 721-3-3 / 04.90
DIN VDE 0110 Part 1 / 01.89
moisture not permitted
DIN VDE 0110 Part 2 / 01.89
DIN VDE 0160 / 04.91
DIN VDE 0470 Part 1 / 11.92 = ∧ EN 60529
IEC 801-2, IEC 801-4
DIN IEC 68-2-6 / 06.90
Constant amplitude of
deflection
acceleration
2
mm
m/s
0.075
9.8 (1)
3.5
9.8 (1)
https://www.aotewell.com
Sales@aotewell.com
Technical Data
(g)
14-1

Hide quick links: