Siemens Simovert 6SE70 Series Operating Instructions Manual page 26

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
Connection
Function
Incoming supply terminals
Protective conductor
Power feedback terminals
autotransformer/system
Power terminals
DC link voltage
(inverter)
Fan terminals
Sizes E, H, K
Table 3.1
Power connections
Sizes C and E
Terminal X19 fused with fuse (F3 and F4):
T2A/250V time-lag 6.3x32 mm (¼" x 1¼")
(19343-T2A/250V Messrs. Wickmann-Werke GmbH or 0034.5231 FST Messrs. Schurter)
or
T2A/250V time-lag 5x20 mm
(19198-T2A/250V Messrs. Wickmann-Werke GmbH or 0034.3993 FSD Messrs. Schurter)
Sizes H and K
Terminal X19 fused with fuse (F3 and F4):
T2A/250V time-lag 6.3x32 mm (¼" x 1¼")
(19343-T7A/250V Messrs. Wickmann-Werke GmbH or 0034.5243 FST Messrs. Schurter)
If the device is operated on a network in which a phase is grounded instead of the
neutral, the plant operator must ensure that fans (terminals X19-1, X19-2) and the main
contactor circuit (terminals X9-4, X9-5) are fed from this phase and the neutral.
If it is not possible to ensure this, the fans and main contactor circuit must be fed from an
isolating transformer.
Moreover, the feed to terminals X19-1, X19-2, X9-4, X9-5 must be implemented via an
isolating transformer if:
3-4
AoteWell LTD
AoteWell Automation Sales Team
Terminal
X1-U1/L1
X1-V1/L2
X1-W1/L3
PE/GND
X4-1U2/1T1
X4-1V2/1T2
X4-1W2/1T3
X1-C/L+
X1-D/L-
X19-1
X19-2
The connection between the protective ground and electronic ground is interrupted
(see Chapter 3.3.3 Terminals on the CUR Module).
The rectifier/regenerating unit is operated in an ungrounded network.
Buy Siemens PLC HMI Drives at AoteWell.com
Connected load / Description
See Technical Data
Chapter 14
See Technical Data
Chapter 14
See Technical Data
Chapter 14
Supply connection for fan
230V AC ±10%, 50 to 60 Hz ±5%
Size E
Current consumption: 0.84A
Size H
Current consumption: at 50 Hz: 2.6 A, at 60 Hz: 3.3 A
Size K
Current consumption: at 50 Hz: 5.2 A, at 60 Hz: 6.6 A
WARNING
Rectifier/Regenerating Unit
Sales@aotewell.com
Siemens AG
6SE7087-6AK85-1AA0
Operating instructions
https://www.aotewell.com
09.02

Hide quick links: