Siemens Simovert 6SE70 Series Operating Instructions Manual page 115

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
09.02
Example 2 : Available:
Required:
♦ Connect-up parameter r035 at the analog output:
P655 "CUR-AA actual values" = 035
♦ Convert the required output range in [%]:
r035 should be taken from the parameter list, Section 5:
Analog output: 100% = P075
Thus, the following is obtained for the range to be represented:
-630 A → -150% (Parameter value PWE1)
+630 A → 150% (Parameter value PWE2)
♦ Define gain factor P656 and offset P657 :
The following is obtained from the formula shown above:
[ ]
G
ain
factor
V
[ ]
Offset
V
To be adjusted: Gain
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
P075 (rated DC current) = 420 A
Map the output current r035 between -630 and +630 A to -10.00 V to
+10.00 A at the analog output
[ ]
[ ]
(
)
×
U
V
U
V
100
off1
off2
=
[ ]
[ ]
PWE
%
PWE
%
1
2
×
20.00
V
100
%
=
=
6.67
300
%
[ ]
Gain
factor
=
U
V
off1
100
=
+
=
10
V
1
0.00
V
0.00
P656 = +6,67 V
offset
P657 = 0,00 V
Buy Siemens PLC HMI Drives at AoteWell.com
represented as V off1 = -10.00 V
represented as V off2 = +10.00 V
%
(
10.00
V
10.00
=
-
150
%
150
V
[ ]
[ ]
×
V
PWE
%
1
=
10V
%
V
Sales@aotewell.com
×
V)
100
%
%
(
)
×
6.67
V
-
150.00
%
100
%
https://www.aotewell.com
Start-Up
4-33