Setpoints - Siemens Simovert 6SE70 Series Operating Instructions Manual

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
Start-Up
4.3.1.3

Setpoints

The only possible setpoint selection that can be programmed on a rectifier/regenerating unit is the selection of
the Id setpoint for a rectifier/regenerating unit in slave mode (e.g. the slave rectifier/regenerating unit in 12-pulse
operation) using parameter
(See also Chapter 5 "Parameter list")
The control word command can be used for effecting the changeover:
"Basic and reserve settings"
See Section 4.4 "Function diagrams"
The source for the setpoint is defined using values:
Value entry in
Index1 i001
Index2 i002
Value assignment for P486 "Source Id-setpoint" :
Value
0000
Constant setpoint = 0
2002
SST1 (PMU -X300 or -X100:1...5) Word2
2003
2004
...
2016
3002
3003
3004
...
3016
4101
SCB1 with SCI 1,Slave1, analog input AE1
4102
4103
4201
SCB1 with SCI 1,Slave2, analog input AE1
4202
4203
4501
SCB-SST (only Peer to Peer, Word1)
4502
USS /Peer to Peer, Word2
4503
USS /Peer to Peer, Word3
4504
USS /Peer to Peer, Word4
4505
USS /Peer to Peer, Word5
4506
...
4516
6002
SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word2
6003
SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word3
6004
SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word4
6005
SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word5
4-28
AoteWell LTD
AoteWell Automation Sales Team
active when "basic setting" selected" (control word)
active when "reserve setting" selected (control word)
Source
Word3
Word4
consecutively to
Word16
OPTIONS
CB/TB Word2
Word3
Word4
consecutively to
Word16)
AE2
AE3
AE2
AE3
only USS, Word6
consecutively to
only USS, Word6
Buy Siemens PLC HMI Drives at AoteWell.com
Factory setting: P486 i001, i002
⇐ only if word 4 is not assigned for "control
word 2 with 2004 (Section 4.3.1.1)
⇐ only if word 4 is not assigned for "control
word 2 with 3004 (Section 4.3.1.1)
⇐ only if word 1 is not assigned for "control
word 1 with 4501 (Section 4.3.1.1)
⇐ only if word 4 is not assigned for "control
word 2 with 4504 (Section 4.3.1.1)
Siemens AG
Rectifier/Regenerating Unit
https://www.aotewell.com
Sales@aotewell.com
09.02
6SE7087-6AK85-1AA0
Operating Instructions