09.02
PNU
OP1S parameter name
Description
*
: Conf.
Par.
P053
Parameter Access
Release of interfaces for parameterization.
*
This parameter is also available as P927 in keeping with Profibus Profile
DVA.
0:
none
1:
COM BOARD
2:
BASE KEYPAD
4:
BASE SERIAL (SST1)
8:
Serial I/O (SCB with USS))
16:
TECH BOARD
Description for Setting:
Every interface is coded by a number.
Input of the number or the total of several numbers which are related to
interfaces, gives parameterization access to these interfaces.
Example:
The factory setting '6' (=4+2) means, that BASE KEYPAD (PMU) and
BASE SERIAL (SST1) have parameterization access.
PNU=35Hex;
Type=O2; Scaling: 1Hex
P054
Display Light
Backlight for the optional operation panel OP
0 = Backlight always ON
1 = Backlight only ON during operation
PNU=36Hex;
Type=O2; Scaling: 1Hex
P055
Copy Parameters
This parameter permits the copying of data sets 1, 2, 3 or 4 to data sets 1,
*
2, 3 or 4.
Only those parameters specified in Section 4.4 "Selecting the data sets" are
affected by the copying process whereby each of these parameters has 4
indices that are assigned to the 4 data sets.
Data set 1 can be set with the parameters Pxxx i001
Data set 2 can be set with the parameters Pxxx i002
Data set 3 can be set with the parameters Pxxx i003
Data set 4 can be set with the parameters Pxxx i004
0xy
Do nothing; automatic reset value at the end of a copy
operation
1xy
The contents of data set x (x = 1, 2, 3 or 4) are copied to data
set y (y = 1, 2, 3 or 4) (data set x remains unchanged; the
original contents of data set y are overwritten).
x and y are the respective data set numbers (1, 2, 3 or 4) of the
source and destination data set.
Each copy operation is started by changing P055 to parameter mode if
P055 = xy and the unit is not in the "RUN" status. P555 is reset to P055 =
0xy at the end of the copy operation.
Important: Once a copy operation has been started, the electronic
power supply must not be switched off for at least 3 minutes to
enable the copied parameters to be passed to the EEPROM.
P055 is not stored in the EEPROM, and has the value "012" when the
electronic power supply is switched on.
PNU=37Hex;
Type=L2; Scaling: 1Hex
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
(CB)
(PMU)
(SST1 and OP)
(SCB)
(TB)
∧ 1
=
∧ 1
=
∧ 1
=
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Value range
Display
[phys. unit]
Indices
Selection text
Factory-
setting
0 to 31
-
6
0 to 1
-
0
always ON
dur. operat.
011 to 144
-
012
https://www.aotewell.com
Parameter List
See
Modify
(access /
status)
1/UHABR
1/ HABR
3/
BR
3/
BR
3/
B
3/
B
5-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents