Siemens Simovert 6SE70 Series Operating Instructions Manual page 219

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
09.02
When replaced under MLFB 6SE7090-0XX85-1DA0, the PCB electronics CUR (C98043-A1680) is supplied
programmed without EPROM (software). The EPROM programmed (last state) must be ordered separately,
as must the operating instructions for a new software version.
Example of replacement part ordering of a CUR with accessories:
PCB electronics (CUR)
EPROM programmed
Operating instructions rectifier/regenerating Unit unit
e.g. English
Assigning the "Start-up" parameters for the CUR option module (A10)
For general information see Chapter 4
F060
P and Higher key
P051 = 3
P052 = 2
P070 =
P052 = 0
P and Lower key
P-key
See Section
4.2.2 or 4.2.3
Replacing firing-circuit module A23
Carry out circuit identification after replacing the A23 (see Chapter 4).
Sizes H and K
The earth connection must be restored by tightening the screws marked with an
earthing sign on the electronics box (size H) or on the electronics slide-in unit (size K).
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating instructions
AoteWell LTD
AoteWell Automation Sales Team
NOTE
Switch over from fault display to parameterization
Access stage "Expert mode"
MLFB setting (initialization)
Initialization is mandatory.
Specify the ID number of the MLFB in P070 of the
rectifier/regenerating unit (rating plate on the unit) as
per MLFB table Section 4.3.9.2.
Return from setting MLFB
Change back to fault display and acknowledge F060
Buy Siemens PLC HMI Drives at AoteWell.com
6SE7090-0XX85-1DA0
6SW1701-0DA14
6SE7087-6AK85-1AA0
WARNING
WARNING
Sales@aotewell.com
Maintenance
https://www.aotewell.com
8-5