Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
09.02
PNU
OP1S parameter name
Description
*
: Conf.
Par.
P077
Factory set. type
Selective factory setting (see Section 4.3.9.1)
*
The parameter can be modified in the state "MLFB input" (P052=2). There
are two methods for setting the parameters dependent on P077:
1: If a MLFB is not entered (P070=0), once P077 has been entered and
"MLFB input" has been terminated (P052=0), the selected parameter
becomes valid immediately
2: Via the selection "Par.reset" (P052=1 or P970=0), "generate factory
setting" is carried out and the setting of P077 is taken into account. The
values of P070 and P077 will not be changed, but all other parameters
are reset to their factory setting
Parameter values:
0: Factory setting, acc. to "Parameter list", Chapter 5
1: With this setting, the following parameters are initialized differently as
compared to "0"
P554, P555
2: With this setting, the following parameters are initialized differently as
compared to "0"
P554, P555, P565, P566, P567, P575, P588, P607
4: With this setting, the following parameters are initialized differently as
compared to "0"
P554, P555, P565, P566, P575, P588, P607
5: With this setting, the following parameters are initialized differently as
compared to "0"
P486, P554, P555, P561, P565, P566, P567, P572, P575, P583, P587,
P588, 607
6: With this setting, the following parameters are initialized differently as
compared to "0"
P486, P554, P555, P561, P565, P566, P572, P575, P583, P587, P588,
P607
PNU=4DHex; Type=02; Scaling: 1Hex
r089
Module slot1
Module in slot 1 (left) in the electronics box.
4 = Module CUR
(Designation: RRU=Rectifying Regenerative Unit)
PNU=59Hex;
Type=02; Scaling: 1Hex
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
∧ 1
=
∧ 1
=
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Value range
Display
[phys. unit]
Indies
Selection text
Factory-
setting
0 to 6
-
0
RRU
4
-
-
RRU
https://www.aotewell.com
Parameter List
See
Modify
(access /
status
3/U BR
3/U
3/ B
5-9