Status Word (Status Word 1 And Status Word 2); Introduction And Application Example - Siemens Simovert 6SE70 Series Operating Instructions Manual

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
09.02
4.3.1.2

Status word (status word 1 and status word 2)

4.3.1.2.1

Introduction and application example

Status words 1 (bits 0 to 15) and 2 (bits 16 to 31) issue messages and commands from the
rectifier/regenerating unit to external destinations.
Their particular status can be read-out via parameters r552 or r968 (status word 1) and r553 (status word 2).
An overview is provided in Section 4.3.1.2.2 "Overview of the status word".
The significance of the possible messages and commands to the outside is described in Section 4.3.1.2.4
"Significance of the status word messages".
Each status word bit is assigned a selection parameter, which defines, to which destination this bit is sent (refer
to Section 4.3.1.2.2, right-hand column).
The selection parameters for the destinations are indexed twice as follows:
Index: i001
i002
An overview of the possible destinations, which are assigned fixed values, is provided in Section 4.3.1.2.3
"Selecting the destinations for the status word".
For the output of faults, alarms and switch-on inhibit of the status word ( HIGH active ) via the terminal strip,
then these are LOW active at the terminals (binary outputs) (i.e.: the relay drops out)!
This is also true for possible option boards!
Also refer to Section 4.3.3 "Binary outputs"
Example:
Status word bit
0
Meaning
Select
P600
P600
P600
parameter
Term. on CUR
i001=
Term on SCI 1/2
i002=
Value
0000 1001 1002
Dest.
Index 1
Terminal on CUR
"Run" signal:
- at terminal -X104:19/20 of the CUR
- at terminal of the binary output 5 of the SCI (option),which is coded as slave 2
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
Selecting a terminal on the CU / PEU board (basic converter)
Selecting a terminal on the SCI 1/2 board (option)
1
2
3
P601
P602
P603
i001=
i001=
i001=
i002=
i002=
i002=
0000 4101 ...
4112 4201 ...
Index 2
Terminal on SCI 1/2
(Option)
Buy Siemens PLC HMI Drives at AoteWell.com
NOTE
...
...
P...
P...
P631
i001=
i001=
i001=
i002=
i002=
i002=
4205 ...
4212
Sales@aotewell.com
31
https://www.aotewell.com
Start-Up
4-23