Siemens Simovert 6SE70 Series Operating Instructions Manual page 190

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
Parameter List
PNU
OP1S parameter name
Description
*
: Conf.
Par.
P694
CB/TB Act Values
Actual-value output over the serial interface of the CB and/or TB module
*
Defines which parameter is to be transferred at which telegram address.
Note:
Word 1 should be set for status word 1 (r552=r968)
If the value "0" is entered (factory settings from i002 to i016), the constant
value "0" is passed on.
i001 Word 01 of the (process data part of the) telegram
i002 Word 02 of the (process data part of the) telegram
...
i016 Word16 of the (process data part of the) telegram
PNU=2B6Hex; Type=O2; Scaling: 1Hex
P695
CB/TB TlgOFFTime
Telegram lag time of CB and TB
*
If no correct telegram is received within the parameterized time a fault trip is
set.
Monitoring is carried out at intervals of 20 ms, therefore it is only appropriate
to set values that are multiples of 20 ms.
Description for setting:
0:
no monitoring, no fault trip; must be parameterized for sporadic
(non-cyclic) telegrams, e. g. operator panel OP at serial comm.
interface 1.
PNU=2B7Hex; Type=O2; Scaling: 1Hex
P696
CB Parameter 1
Communication board parameter 1.
See manual of the used communication board.
Parameter is only needed if a communication board is reported (P090 or
P091 = 1)
The communication board checks, if the set value is valid. If the value is not
accepted, the fault message 80 is issued with fault value 5
PNU=2B8Hex; Type=O2; Scaling: 1Hex
P697
CB Parameter 2
Communication board parameter 2
see P696
PNU=2B9Hex; Type=O2; Scaling: 1Hex
P698
CB Parameter 3
Communication board parameter 3
See P696
PNU=2BAHex; Type=O2; Scaling: 1Hex
P699
CB Parameter 4
Communication board parameter 4
See P696
PNU=2BBHex; Type=O2; Scaling: 1Hex
P700
CB Parameter 5
Communication board parameter 5
See P696
PNU=2BCHex; Type=O2; Scaling: 1Hex
P701
CB Parameter 6
Communication board parameter 6
See P696
PNU=2BDHex; Type=O2; Scaling: 1Hex
5-32
AoteWell LTD
AoteWell Automation Sales Team
∧ 1
=
∧ 1 ms
=
∧ 1
=
∧ 1
=
∧ 1
=
∧ 1
=
∧ 1
=
∧ 1
=
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Value range
Display
[phys. unit]
Indices
Selection text
Factory-
setting
0 to 999
16
i001=968
i002=0
. . .
i016=0
0 to 6500
-
[ms]
20
0 to 65535
-
0
0 to 65535
-
0
0 to 65535
-
0
0 to 65535
-
0
0 to 65535
-
0
0 to 65535
-
0
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
https://www.aotewell.com
09.02
See
Modify
(access /
status)
3/
BR
3/
B
3/
BR
3/
BR
3/ HBR
3/ H
3/ HBR
3/H
3/ HBR
3/ H
3/ HBR
3/ H
3/ HBR
3/ H
3/ HBR
3/ H

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents