Siemens Simovert 6SE70 Series Operating Instructions Manual page 174

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
Parameter List
PNU
OP1S parameter name
Description
*
: Conf.
Par.
P366
Auto Restart
Auto restart after power outage
*
If the power fails at one of the terminals U1/L1, V1/L2, W1/L3, 1U2/1T1,
1V2/1T2 1W2/1T3, X9.1 and X9.2, or if the voltage is not within the
permissible tolerance range and the DC link voltage has dropped beneath
the P074
1.35
*
*
0
Auto restart inhibited
No automatic restart; the corresponding fault message (F003,
F004, F005, F007, F009 or F010) is triggered.
1
Acknowledgment following power outage
The rectifier/regenerating unit enters status o 008 (switch-on
inhibit) or o 009 (switch on/off from the I/O keys of the PMU). On
power recovery, a new ON command must be given to enable
the DC link to re-charge. The inverter is not automatically
restarted by the WEA (auto restart) function.
2
Restart following power recovery and pre-charging of the DC
link
During the power outage, the controllers and firing pulses of the
PZD R/R are inhibited. The rectifier/regenerating unit enters
status o 010. On recovery of the voltage, the DC link is charged
again as quickly as possible (see Section 4.3.10.1).
Important: The necessary external measures must be taken to guarantee
safety on an automatic restart!
PNU=16EHex; Type=O2; Scaling: 1Hex
P408
Caps FormingTime
Forming time of the DC link
This parameter is used when forming the DC link (P052=20).
RDS parameter
PNU=198Hex; Type=O2; Scaling: 1Hex
P409
Contactor Delay
Closing delay of the line contactor
Closing of the line contactor is delayed by the time set here with respect to
the "Switch on" command.
This parameter can be used to implement time grading when energizing the
line contactors of several drive units in order to prevent the inrush currents
of the autotransformers for regenerative mode overloading a supply
transformer.
PNU=199Hex; Type=O2; Scaling: 1Hex
5-16
AoteWell LTD
AoteWell Automation Sales Team
P071 threshold, the S/F unit responds as follows::
∧ 1
=
∧ 0.1
=
∧ 0.1
=
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Value range
Display
[phys. unit]
Indices
Selection text
Factory-
setting
0 to 2
-
0
OFF
ON Reset
ON Always
1.0 to 600.0
4
[min]
10.0
0.0 to +120.0
-
[s]
0.0
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
https://www.aotewell.com
09.02
See
Modify
(access /
status)
3/
BR
3/
BR
2/ ABR
2/ AB
3/ BR
3/ B