4.3.9.3
Download or upread (P052 = 3)
P052 has to be set to 3 when a "download" (write) or "upload" (read) has to be carried out for the parameters of
the rectifier/regenerating unit at the basic unit interface (SST1) using USS protocol (e.g. using D or OP1S).
"Upread/Download" can be selected in the following statuses: "Switch-on inhibit" (008), "Ready-to-switch-on"
(009) or "Fault" (007).
Procedure:
⇓
P052 = 3
⇓
P key
- Using a PC at the basic device interface SST1 and an appropriate application program (e.g.
DriveMonitor), it is possible to read and change all parameters independently of their
operating state and access level (P051).
⇓
P052 = 0
⇓
P key
⇓
After return, the operating display appears, "Switch-on inhibit" (008) or "Ready-to-switch-on"
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
Function selection "Upread/Download
The operating display appears(021)
Function selection Return
(009)
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Start-Up