Parameter List
PNU
OP1S parameter name
Description
*
: Conf.
Par.
5.16

Profile parameters

P917
Change Reports
Control word for spontaneous messages
*
If the value of an active parameter is changed, the new value is reported to
the programmable controller connected by means of the spontaneous
reporting mechanism. This function can be activated and de-activated for
each interface.
Important:
When the control word is modified, spontaneous message buffers can be
deleted with the loss of spontaneous messages!
0
No spontaneous messages
1
Output of spontaneous messages over the DPR interface
(TB/CB)
2
Output of spontaneous messages over the BASE SERIAL
interface (SST1)
4
Output of spontaneous messages over SCB with USS protocol
Setting help:
Each interface is coded with a number.
Enter the number and/or the sum of several numbers assigned to the
interfaces to enable the spontaneous message mechanism for the relevant
interface(s).
PNU=395Hex; Type=O2; Scaling: 1Hex
P918
CB Bus Address
Protocol depending bus address for communication board; see manual of
this board.
Notes:
The communication board checks, if the set value is valid. (Bus addresses 0
to 2 are reserved for master stations). If the value is not accepted, the fault
message 80 is issued with fault value 5
Condition:
P090=1 or P091=1 (communication board installed)
PNU=396Hex; Type=O2; Scaling: 1Hex
P927
Parameter Access
Release of interfaces for the parameterization.
*
This parameter performs the same function as P053.
Parameter P053 can always be modified.
For description, see P053.
PNU=39FHex; Type=O2; Scaling: 1Hex
P928
Src Base/Reserve
Source of the switching command 'base / reserve settings' (control word 2,
*
bit 30)
This parameter performs the same function as P590.
For description, see P590.
PNU=3A0Hex; Type=L2; Scaling: 1Hex
5-38
AoteWell LTD
AoteWell Automation Sales Team
∧ 1
=
∧ 1
=
∧ 1
=
∧ 1
=
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Value range
Display
[phys. unit]
Indices
Selection text
Factory-
setting
0 to 7
-
0
inactive
TB/CB
SCom
SCB (USS)
0 to 200
-
3
0 to 31
-
6
0 to 6005
-
1005
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
https://www.aotewell.com
09.02