09.02
4.3.1.4

Actual values

All available parameter numbers (0 to 999) can be entered into the actual value parameters, sorted according to
destinations (refer to the following).
The parameter value of the entered parameter number is output at the selected destination.
Note:
- When specifying parameter numbers, which are indexed, the value of the first index (.i001) is always
output!
- When specifying "0", no output is made to the appropriate destination!
Destinations:
P655
"CUR-AA actual values"
Output via the CUR control terminal strip (Section 3.3)
Analog output 1 (-X102:14 / reference potential -X102:15)
(refer to Section 4.3.5 "analog output")
P680
"SST1 actual values"
Output via the basic converter interface SST1
Indices:
(refer to Section 4.3.6.1 "basic converter interface SST1")
Destination, options:
P664
"SCI-AA actual values"
Output via the SCB1 interface with SCI1
(also refer to the Instruction Manual for the option boards)
Indexes
i001
i002
i003
i004
i005
i006
P690
"SCB actual values"
Output via the SCB1 interface with peer-to-peer protocol or SCB2
(also refer to the Instruction Manual for the option boards)
Indexes:
i001
i016
P694
"CB/TB actual values"
Output via the CB or TB interface
(also refer to the Instruction Manual for the option boards and Sections 4.3.6.2 "DPR")
Indices:
i001
i016
For telegram data transfer (P680,P690,P694), it is generally necessary/practical to assign "Word 01 of the
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
i001
Word 01 of the telegram (PZD)
i016
Word 16 of the telegram (PZD)
Destination: Analog output 1 from slave 1
Destination: Analog output 2 from slave 1
Destination: Analog output 3 from slave 1
Destination: Analog output 1 from slave 2
Destination: Analog output 2 from slave 2
Destination: Analog output 3 from slave 2
Destination: Word 01 of the telegram (PZD)
Destination: Word 16 of the telegram (PZD)
Destination: Word 01 of the telegram (PZD)
Destination: Word 16 of the telegram (PZD)
telegram (PZD)" with status word 1 (r968 or r552)!