General Observation Parameters - Siemens Simovert 6SE70 Series Operating Instructions Manual

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
Parameter List
PNU
OP1S parameter name
Description
*
: Conf.
Par.
5.2

General observation parameters

r001
Status
Observation parameters for the current status of the S/F unit
0 = Enter MLFB (P070)
1 = Establish factory setting
2 = Hardware initialization
4 = Hardware settings
5 = Drive system settings
7 = Fault
8 = Restart inhibit
9 = Ready for turn-ON
10 = Wait for system voltage
11 = Ready for operation
12 = Ground fault test
14 = R/R unit is in operation
15 = Ramp generator decelerating (OFF1)
18 = Circuit identification or forming
21 = Download of parameter settings
PNU=1Hex;
Type=O2; Scaling: 1Hex
r006
DC Bus Volts
Actual DC link voltage
PNU=6Hex;
Type=I2; Scaling: 1Hex
r011
Heatsink Temp
Temperature of the heat sink
PNU=0BHex; Type=I2; Scalling: 1Hex
r012
Base/Reserve
Base / reserve settings of the process data wiring for control word bits
0:
Base setting
1:
Reserve setting
PNU=0CHex; Type=O2; Scaling: 1Hex
r013
Operat. Hours
Display of operating hours with firing pulses enabled (Run status).
All times > about 0.1s are taken into account.
i001 = days (0..9999)
i002 = hours (0..24)
i003 = seconds (0..3600)
The operating hours counter r013 is set to 0 when the factory setting is
established (P052=1).
PNU=0DHex; Type=O2; Scaling: 1Hex
r030
Rectifier Volts
Display of the system voltage at the rectifier bridge (phase W-U)
PNU=1EHex; Type=O2; Scaling: 1Hex
r031
Inverter Volts
Display of the system voltage at the regenerative bridge (average value of
the three phases)
PNU=1FHex;
Type=O2; Scaling: 1Hex
5-4
AoteWell LTD
AoteWell Automation Sales Team
∧ 1
=
∧ 1 V
=
∧ 0 to 16384V
=
0 - 100%
∧ 1 °C
=
PZD gr.: 1
∧ +/-100 °C
=
Analog output: +/-100%
∧ 1
=
∧ 1
=
∧ 0.1 V
=
∧ 0 to 1638.4V
=
0 - 100%
∧ 0.1 V
=
∧ 0 to 1638.4V
=
0 - 100%
Buy Siemens PLC HMI Drives at AoteWell.com
Value range
[phys. unit]
Selection text
0 to 21
(U)
MLFB-Input
Init. RFE
(H)
InitHW Conf
(H)
HW Config.
(A)
System Set.
(B)
Fault
(B)
ON Locked
(B)
Ready for ON
(B)
Line Voltage
(B)
Ready Oper
(B)
GrndFltTest
(R)
Operation
(R)
OFF 1
(R)
Circuit ID
(B)
Download
0 to 1000
[V]
-53 to 199
[°C]
0 to 1
d
h
s
0.0 to 1000.0
[V]
0.0 to 1000.0
[V]
Siemens AG
Rectifier/Regenerating Unit
https://www.aotewell.com
Sales@aotewell.com
09.02
Display
See
Indices
Modify
Factory-
(access /
setting
status)
-
2/UHABR
-
2/
BR
-
-
3/
BR
-
-
2/
BR
-
3
2/
BR
-
-
2/
BR
-
-
2/
BR
-
6SE7087-6AK85-1AA0
Operating Instructions