09.02
Fault
Fault description
No.
F082
TB/CB Telegr
TB/CB telegram failure
The exchange of data has been
interrupted.
P695 defines the telegram failure time
F090
Circuit ID F
Circuit identification not possible
F091
Circuit ID C
Circuit identification or forming aborted
due to external cause.
If circuit identification is aborted, only
those parameters are modified whose
assignment was completed before this
fault occurred.
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
AoteWell LTD
AoteWell Automation Sales Team
Fault
Meaning
value
CB alarm channel faulty
1
2
TB alarm channel faulty
3
TB error channel faulty
4
CB task channel (CB
5
CB answer channel (CUR
faulty
6
Internal error
7
TB task channel (TB
8
TB answer channel (CUR
faulty
9
Internal error
10
CB/TB Telegram failure
11
PMU task channel (CUR
faulty
12
PMU answer channel (TB
faulty
21
CB/TB setpoint channel faulty
22
CB/TB actual value channel faulty
1
If generating mode is inhibited
(P076 = xx1), circuit identification is
not possible!
2
α
If
current flows (less than 25% of the
rated DC current with
P160=150.0% or less than 10%
with P160=60.0%)
3
P141 (Rectifier Induct.) and/or
P143 (Inverter Induct.) and/or P144
(C for DC link) could not be
identified
4
A waiting time of 20s has already
elapsed but the circuit identification
cannot be carried out because the
DC link voltage is too high
(Ud>20% of 1.35 * P071)
1
The abort took place because the
RUN or "R" status was exited for
some reason (e.g. brief power
outage) during forming or circuit
identification.
2
The abort took place because the
reserve data set selection changed
during forming or circuit
identification.
3
The abort took place because the
OFF command was given.
4
The abort took place because an
ON command was not given within
20 sec after selecting the forming
function (P052=20) or the circuit
identification function (P052=21)
5
The abort took place because the
"Inhibit regenerating" command
was given during circuit
identification (see control word 1,
bit 12 and P572)
Buy Siemens PLC HMI Drives at AoteWell.com
CUR) faulty
CB)
CUR) faulty
TB)
TB)
CUR)
= 30°, not enough rectifier
Sales@aotewell.com
Fault and Alarm Messages
Possible causes
Countermeasures
-
- Set P076 = x2
- Connection to DC link interrupted
- Commutating inductance too low
(see Section 3.1)
- Connection to DC link interrupted
- Another unit is supplying the DC
link
- Wait until the DC link has
discharged sufficiently, then start
circuit identification again
-