Siemens Simovert 6SE70 Series Operating Instructions Manual page 180

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
Parameter List
PNU
OP1S parameter name
Description
*
: Conf.
Par.
P587
Src Master/Slave
Source for the master/slave drive changeover (control word 2, bit 27)
*
0:
Master drive: The control works with an internal current setpoint
1:
Slave drive: The control works with an external current setpoint
Other values: see allowed settings in Section 4.3.1.1 (process data
B/R parameter
PNU=24BHex; Type=L2; Scaling: 1Hex
P588
Src No Ext Warn1
Source of the 'External warning 1' message (control word 2, bit 28)
*
0:
Not allowed
1:
No external warning
Other values:
see allowed settings in Section 4.3.1.1 (process data wiring of
the control word)
B/R- parameter
PNU=24CHex; Type=L2; Scaling: 1Hex
P589
Src No Ext Warn2
Source of the 'external warning 2' message (control word 2, bit 29))
*
0:
Not allowed
1:
No external warning
Other values: see allowed settings in Section 4.3.1.1 (process data
B/R parameter
PNU=24DHex; Type=L2; Scaling: 1Hex
P590
Src Base/Reserve
Source of the 'Base / reserve settings' switching command (control word 2,
*
bit 30)
0:
Base setting
1:
Reserve setting
1005: Binary input 5 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
No base/reserve changeover possible
PNU=24EHex; Type=L2; Scaling: 1Hex
P591
Src ContactorMsg
Source of the 'Main contactor energized' message(control word 2, bit 31)
*
0:
1:
1001 to 1005: CUR terminals
4101 to 4116: SCB-SCI1- terminals (serial I/O)
4201 to 4216: SCB-SCI2- terminals (serial I/O)
For details see Section 4.3.1.1
Notes:
If the function is active, pulses are released as soon as the message is
available.
No base / reserve settings possible
PNU=24FHex; Type=L2; Scaling: 1Hex
5-22
AoteWell LTD
AoteWell Automation Sales Team
wiring of the control word)
∧ 1
=
∧ 1
=
wiring of the control word)
∧ 1
=
wiring of the control word)
∧ 1
=
Not allowed
No main contactor checkback signal
∧ 1
=
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Value range
Display
[phys. unit]
Indices
Selection text
Factory-
setting
0 to 6005
2
(0)
1 to 6005
2
(1)
1 to 6005
2
1
0 to 6005
-
1005
1 to 4216
-
1
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions
https://www.aotewell.com
09.02
See
Modify
(access /
status)
2/
BR
2/
BR
3/
BR
3/
BR
3/
BR
3/
BR
3/
BR
3/
BR
3/
BR
3/