10.43 Thyristor diagnosis
P830
Control word for thyristor diagnosis
*
0
Thyristor check function deactivated
1
Thyristors are checked on initial SWITCH-ON or INCHING
command after connection of the electronics supply voltage.
2
Thyristors are checked on every SWITCH-ON or INCHING
command.
3
Thyristors will be checked on the next SWITCH-ON or INCHING
command. Parameter P830 is set to 0 if no fault is detected.
Note:
The thyristor check function may not be activated (setting P830=0 must be
selected)
when the "Enable a torque direction for torque direction change by
parallel drive" function is in use (see also parameter P165) or
when the converter is used to supply large inductances (e.g. field supply
from armature terminals, supply of lifting solenoids, etc.).

10.44 Parameters for DriveMonitor and OP1S

P831
Parameters for the Trace function of DriveMonitor
to
These parameters are settings for the data exchange between DriveMonitor
r849
and the SIMOREG converter. They must not be changed!
r850
Parameters for the OP1S
to
These parameters are settings for the data exchange between OP1S and
P899
the SIMOREG converter. They must not be changed!

10.45 Profile parameters

P918
CB bus address
Protocol-dependent bus address for communication boards
(Z110)
Note:
(Z111)
The validity of the bus address is monitored by the communication board.
(Bus addresses 0 to 2 are reserved for Master stations on PROFIBUS
boards and must not therefore be set for other purposes). If the value is not
accepted by the COM BOARD, fault F080 is displayed with fault value 5
P927
Parameterization enable
*
Enabling of interfaces for parameterization. A parameter value can only be
(G170)
altered via an enabled interface.
(G171)
0:
None
(G172)
(Z110)
1:
Communications board (CB)
2:
Parameterizing unit (PMU)
(Z111)
4:
G-SST1 serial interface and OP1S
8:
Reserved
16:
Technology board (TB)
32:
G-SST2 serial interface
64:
G-SST3 serial interface
Setting information:
Every interface has a numeric code.
The number for one specific interface, or the sum of various numbers
assigned to several interfaces, must be entered in this parameter in order to
enable the relevant interface(s) for use as a parameterization interface.
Example:
Factory setting value 6 (=4+2) means that the PMU and G-SST1 interfaces
are enabled for parameterization purposes.
10-88
Value range
[Unit]
Steps
0 to 3
1
0 to 200
1
0 to 127
1
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
P052 = 3
P052 = 3
Ind: 2
P052 = 3
FS=3
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=6
P051 = 40
Type: V2
Offline

Advertisement

   Also See for Siemens 6RA70 Series

   Related Manuals for Siemens 6RA70 Series

Comments to this Manuals

Symbols: 0
Latest comments:
  • Rolando Guevarra Jan 02, 2018 12:48:
    Hi, i have trouble in our drive, F019, anyone can help to solve this fault. Thanks in advance
  • vivek Kumar Jul 28, 2015 05:25:
    6ra70 drive 250 kw problem field weakning optimizati​on failed fault f050 fault valu 10 plz help... m
  • vk jadaun Jul 18, 2015 02:16:
    242 kw dc drive but problem optimizati​on fail 25 current and field fault F050 fault valu 3.... ... plz suggest...