Tests
3.1 Visual inspection
3.1.5

Cable markings

Fundamentals
A visual inspection is made to see whether cables and conductors are marked as defined in the
circuit diagram.
Test procedure
1. The customer selects cables or conductors by random sampling.
Result
The test is passed if the cable and conductor markings match what is specified in the circuit
diagram.
3.1.6

Setting values of circuit breakers, if used

Fundamentals
The circuit breaker settings are visually checked against what is specified in the circuit diagram.
Test procedure
1. The customer selects circuit breakers by random sampling.
2. The circuit breaker settings are visually checked against what is specified in the circuit
Result
The test is passed if the circuit breaker settings match what is specified in the circuit diagram.
3.1.7

Dimensions

Fundamentals
The drive dimensions are measured. The basis for the visual inspection is the order-specific
dimension drawing.
Test procedure
1. The external dimensions, length, width and height of the drive are measured.
20
– Are the cable end tags and conductor colors of cables and conductors marked as defined
in the circuit diagram?
diagram.
SINAMICS GL150 6SL3850 F03 F70 F98 E11