Tests
3.2 Function test
Test procedure
1. The auxiliary voltage is present.
2. The signal cable for signaling the ground fault is interrupted.
Result
The test is passed if the ground fault message is displayed on the test station computer.
3.2.8

Message "Disconnector cabinet door"

Fundamentals
The test reveals whether a message is displayed on the test station computer when the
disconnector cabinet door is open.
Test procedure
1. The auxiliary voltage is present.
2. The signal cable for signaling the message "Disconnector cabinet door" is interrupted.
Result
The test is passed if the message "Disconnector cabinet door" is displayed on the test station
computer.
3.2.9

Failure of actual value acquisition

Fundamentals
The test reveals whether the drive switches off when actual value acquisition is defective.
Test procedure
1. The auxiliary voltage is present.
2. The cable 1N24V DC for the power supply for the AVT combination of the actual value
Result
The test is passed if the drive responds as described.
26
acquisition is interrupted. This simulates a failure of actual value acquisition.
The drive switches itself off. A fault is displayed on the test station computer.
SINAMICS SL150 6SL3860 F03 F70 F98 F79 F76