Fuses And Circuit Breakers - Danfoss VLT AutomationDrive FC 302 Design Manual

90–710 kw, enclosure sizes d and e
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Electrical Installation Con...

10.5 Fuses and Circuit Breakers

Fuses ensure that possible damage to the drive is limited to damages inside the unit. To ensure compliance with EN 50178,
use the recommended fuses as replacements. Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009
(UL) compliant installations.
D1h–D8h recommended fuses
Type aR fuses are recommended for enclosures D1h–D8h. See Table 10.9.
Model
N55K
N75K
N90K
N110
N132
N160
N200
N250
N315
Table 10.9 D1h–D8h Power/semiconductor Fuse Sizes
Model
Bussman
Littelfuse
N90K
170M2619 LA50QS300-4
N110
170M2620 LA50QS350-4
N132
170M2621 LA50QS400-4
N160
170M4015 LA50QS500-4
N200
170M4016 LA50QS600-4
N250
170M4017 LA50QS800-4
Table 10.10 D1h–D8h Power/semiconductor Fuse Options, 380–500 V
Model
Bussmann
N55K
170M2616
N75K
170M2619
N90K
170M2619
N110
170M2619
N132
170M2619
N160
170M4015
N200
170M4015
N250
170M4015
N315
170M4015
Table 10.11 D1h–D8h Power/semiconductor Fuse Options, 525–690 V
Bussmann
LPJ-21/2SP
Table 10.12 D1h–D8h Space Heater Fuse Recommendation
If the drive is not supplied with a mains disconnect, contactor, or circuit breaker, the Short Circuit Current Rating (SCCR) of
the drives is 100000 A at all voltages (380–690 V).
If the drive is supplied with a mains disconnect, the SCCR of the drive is 100000 amps at all voltages (380–690 V).
If the drive is supplied with a circuit breaker, the SCCR depends on the voltage. See Table 10.13.
MG38C202
Design Guide
380–500 V
ar-315
ar-350
ar-400
ar-500
ar-630
ar-800
Fuse Options
Littelfuse
Bussmann
Siba
L50S-300
FWH-300A
20 189 20.315
L50S-350
FWH-350A
20 189 20.350
L50S-400
FWH-400A
20 189 20.400
L50S-500
FWH-500A
20 610 31.550
L50S-600
FWH-600A
20 610 31.630
L50S-800
FWH-800A
20 610 31.800
Siba
Ferraz-Shawmut European
20 610 31.160
6,9URD30D08A0160
20 610 31.315
6,9URD31D08A0315
20 610 31.315
6,9URD31D08A0315
20 610 31.315
6,9URD31D08A0315
20 610 31.315
6,9URD31D08A0315
20 620 31.550
6,9URD32D08A0550
20 620 31.550
6,9URD32D08A0550
20 620 31.550
6,9URD32D08A0550
20 620 31.550
6,9URD32D08A0550
Danfoss A/S © 01/2018 All rights reserved.
525–690 V
Ferraz-
Ferraz-Shawmut
Shawmut
(Europe)
A50QS300-4
6,9URD31D08A0315
A50QS350-4
6,9URD31D08A0350
A50QS400-4
6,9URD31D08A0400
A50QS500-4
6,9URD31D08A0550
A50QS600-4
6,9URD31D08A0630
A50QS800-4
6,9URD32D08A0800
Ferraz-Shawmut North American
A070URD30KI0160
A070URD31KI0315
A070URD31KI0315
A070URD31KI0315
A070URD31KI0315
A070URD32KI0550
A070URD32KI0550
A070URD32KI0550
A070URD32KI0550
Rating
2.5 A, 600 V
ar-160
ar-315
ar-315
ar-315
ar-315
ar-550
ar-550
ar-550
ar-550
Ferraz-Shawmut
(North America)
A070URD31KI0315
A070URD31KI0350
10
A070URD31KI0400
A070URD31KI0550
A070URD31KI0630
A070URD31KI0800
151
10

Advertisement

Table of Contents
loading

Table of Contents