Danfoss VLT AutomationDrive FC 302 Design Manual page 176

90–710 kw, enclosure sizes d and e
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Electrical Installation Con...
Harmonic order (h)
Table 10.45 Compatibility Levels for Harmonics
THDv
Table 10.46 Compatibility Levels for the Total Harmonic Voltage Distortion THDv
10.16.4 Harmonic Compliance
Danfoss drives comply with the following standards:
IEC61000-2-4
IEC61000-3-4
G5/4
10.16.5 Harmonic Mitigation
In cases where extra harmonic suppression is required, Danfoss offers the following mitigation equipment:
VLT
10
10
VLT
VLT
VLT
Selecting the right solution depends on several factors:
The grid (background distortion, mains unbalance, resonance, and type of supply (transformer/generator).
Application (load profile, number of loads, and load size).
Local/national requirements/regulations (such as IEEE 519, IEC, and G5/4).
Total cost of ownership (initial cost, efficiency, and maintenance).
10.16.6 Harmonic Calculation
Use the free Danfoss MCT 31 calculation software to determine the degree of voltage pollution on the grid and needed
precaution. The VLT
174
5
7
11
13
17
17˂h≤49
2.27 x (17/h) – 0.27
Class 1
5%
®
12-pulse Drives
®
Low Harmonic Drives
®
Advanced Harmonic Filters
®
Advanced Active Filters
®
Harmonic Calculation MCT 31 is available at www.danfoss.com.
Danfoss A/S © 01/2018 All rights reserved.
VLT® AutomationDrive FC 302
Class 1 (V
%)
h
3
3
3
3
2
Class 2 (V
%)
h
6
5
3.5
3
2
2.27 x (17/h) – 0.27
Class 2
8%
Class 3 (V
%)
h
8
7
5
4.5
4
4.5 x (17/h) – 0.5
Class 3
10%
MG38C202