Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 12.2 Wiring Configuration for AMA without
T27 Connected
12.3 Wiring Configurations for Analog
Speed Reference
FC
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
0 – 10 V
COM
39
U - I
A53
Table 12.3 Wiring Configuration for Analog Speed Reference
(Voltage)
MG38C202
Design Guide
Parameters
Function
Setting
Parameter 1-29
[1] Enable
Automatic Motor
complete AMA
Adaptation
(AMA)
Parameter 5-12 T
[0] No
erminal 27
operation
Digital Input
*=Default value
Notes/comments: Set
parameter group 1-2* Motor
Data according to motor
nameplate.
Parameters
Function
Setting
Parameter 6-10 T
0.07 V*
erminal 53 Low
Voltage
Parameter 6-11 T
10 V*
erminal 53 High
Voltage
Parameter 6-14 T
0 RPM
erminal 53 Low
Ref./Feedb. Value
Parameter 6-15 T
1500 RPM
erminal 53 High
Ref./Feedb. Value
*=Default value
Notes/comments:
Danfoss A/S © 01/2018 All rights reserved.
FC
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
4 - 20mA
COM
39
U - I
A53
Table 12.4 Wiring Configuration for Analog Speed Reference
(Current)

12.4 Wiring Configurations for Start/Stop

FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 12.5 Wiring Configuration for Start/Stop Command with
Safe Torque Off
Parameters
Function
Setting
Parameter 6-12 T
4 mA*
erminal 53 Low
Current
Parameter 6-13 T
20 mA*
erminal 53 High
Current
Parameter 6-14 T
0 RPM
erminal 53 Low
Ref./Feedb. Value
Parameter 6-15 T
1500 RPM
erminal 53 High
Ref./Feedb. Value
*=Default value
Notes/comments:
Parameters
Function
Setting
Parameter 5-10 T
[8] Start*
erminal 18
Digital Input
Parameter 5-12 T
[0] No
erminal 27
operation
Digital Input
Parameter 5-19 T
[1] Safe
erminal 37 Safe
Torque Off
Stop
Alarm
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.