Specifications
®
VLT
AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s,
normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft output at 500 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460/500 V) [A]
Intermittent (60 s overload) (at 460/500 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 500 V) [kVA]
Maximum input current
7
7
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Brake or regen [mm
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
- Brake [mm
(AWG)]
- Load share or regen [mm
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Efficiency
3)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C
(°F)]
Table 7.3 Electrical Data for Enclosures E1h/E3h, Mains Supply 3x380–500 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
38
VLT® AutomationDrive FC 302
2
(AWG)]
2
(AWG)]
2
(AWG)]
2
(AWG)]
2
(AWG)]
1)
2), 3)
2), 3)
Danfoss A/S © 01/2018 All rights reserved.
N315
HO
NO
HO
315
355
355
450
500
500
355
400
400
E1h/E3h
600
658
658
900
724
987
540
590
590
810
649
885
416
456
456
430
470
470
468
511
511
578
634
634
520
569
569
5x240 (5x500 mcm)
5x240 (5x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
800
6178
6928
6851
5322
5910
5846
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
± 15% (tolerance relates to variety in voltage and cable conditions). These
N355
N400
NO
HO
400
400
600
550
500
500
E1h/E3h
E1h/E3h
745
695
820
1043
678
678
746
1017
516
482
540
540
587
587
718
670
653
653
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
800
8036
7297
6933
7240
0.98
0.98
0–590
0–590
110 (230)
110 (230)
80 (176)
80 (176)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
NO
450
600
530
800
880
730
803
554
582
632
771
704
8783
7969
MG38C202