Danfoss VLT AutomationDrive FC 302 Design Manual page 178

90–710 kw, enclosure sizes d and e
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Basic Operating Principles ...
LCP keys
[Hand On]
[Hand On]⇒(Off)
[Auto On]
[Auto On]⇒(Off)
All keys
All keys
Table 11.1 Local and Remote Reference Configurations
11.2.2 Remote Handling of References
Remote handling of reference applies to both open-loop
and closed-loop operation. See Illustration 11.3.
Up to 8 internal preset references can be programmed into
the drive. The active internal preset reference can be
selected externally through digital control inputs or
through the serial communications bus.
External references can also be supplied to the drive, most
commonly through an analog control input. All reference
sources and the bus reference are added to produce the
total external reference.
The active reference can be selected from the following:
External reference
Preset reference
11
11
Setpoint
Sum of the external reference, preset reference,
and setpoint
The active reference can be scaled. The scaled reference is
calculated as follows:
Reference  =  X  +  X  ×  
Where X is the external reference, the preset reference, or
the sum of these references, and Y is parameter 3-14 Preset
Relative Reference in [%].
If Y, parameter 3-14 Preset Relative Reference, is set to 0%,
the scaling does not affect the reference.
176
VLT® AutomationDrive FC 302
Parameter 3-13 Reference
Active
Site
Reference
Linked to hand/auto
Local
Linked to hand/auto
Local
Linked to hand/auto
Remote
Linked to hand/auto
Remote
Local
Local
Remote
Remote
Y
100
Danfoss A/S © 01/2018 All rights reserved.
MG38C202