Installations with cables connected in a common joint as shown in A and B are only recommended for short cable lengths.
B
Be aware of the maximum motor cable length specified in chapter 7.6 Cable Specifications.
C
The total motor cable length specified in chapter 7.6 Cable Specifications is valid as long as the parallel cables are kept short less
than 10 m (32 ft) each.
D
Consider voltage drop across the motor cables.
E
Consider voltage drop across the motor cables.
F
The total motor cable length specified in chapter 7.6 Cable Specifications is valid as long as the parallel cables are kept less than
10 m (32 ft) each.
Illustration 10.10 Different Parallel Connections of Motors