Danfoss VLT AutomationDrive FC 302 Design Manual page 44

90–710 kw, enclosure sizes d and e
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Specifications
®
VLT
AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s,
normal overload=110% current during 60 s)
Typical shaft output at 525 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 525 V) [A]
Intermittent (60 s overload) (at 525 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 525 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
7
7
Continuous (at 525 V) [A]
Continuous (at 575/690 V) [A]
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Brake or regen [mm
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
- Brake [mm
(AWG)]
- Load share or regen [mm
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
Efficiency
3)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
Table 7.7 Electrical Data for Enclosures E1h/E3h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
42
VLT® AutomationDrive FC 302
2
(AWG)]
2
(AWG)]
2
(AWG)]
2
(AWG)]
2
(AWG)]
1)
2), 3)
2), 3)
Danfoss A/S © 01/2018 All rights reserved.
N355
HO
NO
HO
315
355
355
400
450
400
355
450
400
E1h/E3h
395
470
429
593
517
644
380
450
410
570
495
615
376
448
409
378
448
408
454
538
490
381
453
413
366
434
395
5x240 (5x500 mcm)
5x240 (5x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
800
4989
6062
5419
4920
5939
5332
0.98
0.98
0–500
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
± 15% (tolerance relates to variety in voltage and cable conditions). These
N400
N500
NO
HO
400
400
500
500
500
500
E1h/E3h
E1h/E3h
523
523
575
785
500
500
550
750
498
498
498
498
598
598
504
504
482
482
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
800
6879
6833
6715
6678
0.98
0–500
0–500
110 (230)
110 (230)
80 (176)
80 (176)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
NO
450
600
560
596
656
570
627
568
568
681
574
549
8076
7852
MG38C202