Parameter 1-01 Motor Control Principle is set to [1] VVC
If parameter 1-00 Configuration Mode is set to [1] Speed closed loop, the resulting reference is passed from the ramp
limitation and speed limitation into a speed PID control. The speed PID control parameters are located in parameter group
7-0* Speed PID Ctrl. The resulting reference from the speed PID control is sent to the motor control limited by the frequency
limit.
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of, for example,
speed or pressure in the controlled application. The process PID parameters are in parameter groups 7-2* Process Ctrl. Feedb
and 7-3* Process PID Ctrl.
11.2.7.2 Control Structure in Flux Sensorless
Ref.
+
11
11
Illustration 11.9 Control Structure in Flux Sensorless Open Loop and Closed-loop Configurations
In Illustration 11.9, the resulting reference from the reference handling system is fed through the ramp and speed limitations
as determined by the parameter settings indicated.
Parameter 1-01 Motor Control Principle is set to [2] Flux Sensorless and parameter 1-00 Configuration Mode is set to [0] Speed
open loop. An estimated speed feedback is generated to the speed PID to control the output frequency. The speed PID must
be set with its P, I, and D parameters (parameter group 7-0* Speed PID control).
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of the
controlled application. The process PID parameters are found in parameter groups 7-2* Process Ctrl. Feedb and 7-3* Process
PID Ctrl.
182
VLT® AutomationDrive FC 302
P 1-00
Con g. mode
Process
PID
_
P 7-20 Process feedback
1 source
P 7-22 Process feedback
2 source
Danfoss A/S © 01/2018 All rights reserved.
+
and parameter 1-00 Configuration Mode is set to [0] Speed open loop.
P 4-13 Motor speed
high limit [RPM]
P 4-14 Motor speed
high limit [Hz]
High
P 3-**
+
Ramp
_
Low
P 4-11 Motor speed
low limit [RPM]
P 4-12 Motor speed
low limit [Hz]
P 4-19
Max. output
freq.
P 7-0*
Motor
Speed
controller
PID
+f max.
-f max.
MG38C202