Application Examples
12.8 Wiring Configuration for RS485
Network Connection
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
61
68
69
12
12
Table 12.11 Wiring Configuration for RS485 Network Connection
188
VLT® AutomationDrive FC 302
Parameters
Function
Setting
Parameter 8-30
FC*
Protocol
Parameter 8-31
1*
Address
Parameter 8-32
9600*
Baud Rate
*=Default value
Notes/comments:
Select protocol, address, and
baud rate in the parameters.
RS-485
+
-
Danfoss A/S © 01/2018 All rights reserved.
12.9 Wiring Configuration for a Motor
Thermistor
NOTICE
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 12.12 Wiring Configuration for a Motor Thermistor
Parameters
Function
Setting
Parameter 1-90
[2] Thermistor
Motor Thermal
trip
Protection
Parameter 1-93 T
[1] analog
hermistor Source
input 53
*=Default value
Notes/comments:
If only a warning is wanted, set
parameter 1-90 Motor Thermal
Protection to [1] Thermistor
warning.
MG38C202