11 Basic Operating Principles of a Drive

This chapter provides an overview of the primary
assemblies and circuitry of a Danfoss drive. It describes the
internal electrical and signal processing functions. A
description of the internal control structure is also
included.

11.1 Description of Operation

A drive is an electronic controller that supplies a regulated
amount of AC power to a 3-phase inductive motor. By
supplying variable frequency and voltage to the motor, the
drive varies the motor speed or maintains a constant
speed as the load on the motor changes. Also, the drive
can stop and start a motor without the mechanical stress
associated with a line start.
In its basic form, the drive can be divided into the
following 4 main areas:
Rectifier
The rectifier consists of SCRs or diodes that convert 3-
phase AC voltage to pulsating DC voltage.
DC link (DC bus)
The DC link consists of inductors and capacitor banks that
stabilize the pulsating DC voltage.
Inverter
The inverter uses IGBTs to convert the DC voltage to
variable voltage and variable frequency AC.
Control
The control area consists of software that runs the
hardware to produce the variable voltage that controls and
regulates the AC motor.
1
2
L1
L2
L3
1
Rectifier (SCR/diodes)
2
DC link (DC bus)
3
Inverter (IGBTs)
Illustration 11.1 Internal Processing
MG38C202
Design Guide

11.2 Drive Controls

The following processes are used to control and regulate
the motor:
11.2.1 User Inputs/References
The drive uses an input source (also called reference) to
control and regulate the motor. The drive receives this
input either:
Active reference
The term active reference refers to the active input source.
The active reference is configured in
parameter 3-13 Reference Site. See Illustration 11.2 and
Table 11.1.
3
For more information, see the programming guide.
Remote
T1
reference
T2
T3
Local
reference
Illustration 11.2 Selecting Active Reference
Danfoss A/S © 01/2018 All rights reserved.
User input/reference.
Feedback handling.
User-defined control structure.
-
Open loop/closed-loop mode.
-
Motor control (speed, torque, or
process).
+
Control algorithms (VVC
, flux sensorless, flux
with motor feedback, and internal current control
+
VVC
).
Manually via the LCP. This method is referred to
as local (Hand On).
Remotely via analog/digital inputs and various
serial interfaces (RS485, USB, or an optional
fieldbus). This method is referred to as remote
(Auto On) and is the default input setting.
Remote
(Auto On)
Linked to hand/auto
(Hand On)
Local
LCP keys:
(Hand On), (O ),
and (Auto On)
11
Reference
P 3-13 Reference Site
175
11