Danfoss VLT AutomationDrive FC 302 Design Manual page 154

90–710 kw, enclosure sizes d and e
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Electrical Installation Con...
Enclosure
D6h
D8h
Table 10.13 D6h and D8h Supplied with a Circuit Breaker
If the drive is supplied with a contactor-only option and is externally fused according to Table 10.14, the SCCR of the drive is
as follows:
Enclosure
D6h
D8h (not including the N250 T5 model)
D8h (N250 T5 model only)
Table 10.14 D6h and D8h Supplied with a Contactor
1)
With a Bussmann type LPJ-SP or Gould Shawmut type AJT fuse. 450 A maximum fuse size for D6h and 900 A maximum fuse size for D8h.
2)
Must use Class J or L branch fuses for UL approval. 450 A maximum fuse size for D6h and 600 A maximum fuse size for D8h.
E1h–E4h recommended fuses
The fuses listed in Table 10.15 are suitable for use on a circuit capable of delivering 100000 A
the drive voltage rating. With the proper fusing, the drive short circuit current rating (SCCR) is 100000 A
drives are supplied with internal drive fusing to meet the 100 kA SCCR and to comply with UL 61800-5-1 enclosed drive
requirements. E3h and E4h drives must be fitted with Type aR fuses to meet the 100 kA SCCR.
Input voltage (V)
380–500
525–690
10
10
Table 10.15 E1h–E4h Fuse Options
Bussmann
LPJ-21/2SP
Table 10.16 E1h–E2h Space Heater Fuse Recommendation
NOTICE
DISCONNECT SWITCH
All units ordered and supplied with a factory-installed disconnect switch require Class L branch circuit fusing to meet
the 100 kA SCCR for the drive. If a circuit breaker is used, the SCCR rating is 42 kA. The input voltage and power rating
of the drive determines the specific Class L fuse. The input voltage and power rating is found on the product
nameplate. For more information regarding the nameplate, see the operating guide.
Input voltage (V)
380–500
380–500
525–690
525–690
152
VLT® AutomationDrive FC 302
415 V
120000 A
100000 A
415 V
IEC
1)
100000 A
100000 A
100000 A
Bussmann ordering number
170M7309
170M7342
Power rating [kW (hp)]
Short circuit rating (A)
315–400 (450–550)
42000
100000
450–500 (600–650)
42000
100000
355–560 (400–600)
40000
100000
630–710 (650–750)
42000
100000
Danfoss A/S © 01/2018 All rights reserved.
480 V
600 V
100000 A
65000 A
100000 A
42000 A
480 V
600 V
UL
2)
UL
100000 A
100000 A
100000 A
100000 A
Consult factory
Not applicable
Rating
2.5 A, 600 V
Required protection
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A
690 V
70000 A
30000 A
690 V
2)
IEC
1)
100000 A
100000 A
Not applicable
(symmetrical), depending on
rms
. E1h and E2h
rms
MG38C202