Safety
2.3.1 ADN-compliant Installation
2
2
To prevent spark formation in accordance with the
European Agreement concerning International Carriage of
Dangerous Goods by Inland Waterways (ADN), take
precautions for drives with protection rating of IP00
(Chassis), IP20 (Chassis), IP21 (Type 1), or IP54 (Type 12).
Do not install a mains switch.
Ensure that parameter 14-50 RFI Filter is set to
[1] On.
Remove all relay plugs marked RELAY. See
Illustration 2.1.
Check which relay options are installed, if any.
The only allowed relay option is VLT
Relay Card MCB 113.
1, 2
Illustration 2.1 Location of Relay Plugs
6
VLT® AutomationDrive FC 302
®
Relay plugs
Danfoss A/S © 01/2018 All rights reserved.