8.7 Fuses and Circuit Breakers

8.7.1 Fuse Recommendations

Fuses ensure that possible damage to the drive is limited to damage inside the unit. Danfoss recommends fuses and/or circuit
breakers on the supply side as protection. For further information, see Application Note Fuses and Circuit Breakers.
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
Recommendations
gG type fuses.
Moeller type circuit breakers. For other circuit breaker types, ensure that the energy into the drive is equal to or lower than the
energy provided by Moeller types.
For further information, see Application Note Fuses and Circuit Breakers.
The recommended fuses in

8.7.2 CE Compliance

(symmetrical), depending on the drive voltage rating. With the proper fusing, the drive short circuit current rating (SCCR) is
10000 A
.
rms
8.7.2 CE Compliance
Table 42: 200–240 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
A1
0.25–1.5 (0.34–2.0)
A2
0.25–1.5 (0.34–2.0)
2.2 (3.0)
A3
3.0 (4.0)
3.7 (5.0)
A4
0.25–1.5 (0.34–2.0)
2.2 (3.0)
A5
0.25–1.5 (0.34–2.0)
2.2–3.0 (3.0–4.0)
3.7 (5.0)
B1
5.5 (7.5)
7.5 (10.0)
B2
11.0 (15.0)
B3
5.5 (7.5)
B4
7.5 (10.0)
11.0 (15.0)
15.0 (20.0)
C1
15.0 (20.0)
18.5 (25.0)
76 | Danfoss A/S © 2021.01
N O T I C E
and
8.7.3 UL Compliance
Recommended
Recommended
fuse size
maximum fuse
gG-10
gG-25
gG-10
gG-25
gG-16
gG-16
gG-32
gG-20
gG-10
gG-32
gG-16
gG-10
gG-32
gG-16
gG-20
gG-25
gG-80
gG-32
gG-50
gG-100
gG-25
gG-63
gG-32
gG-125
gG-50
gG-63
gG-63
gG-160
gG-80
are suitable for use on a circuit capable of 100000 A
Recommended circuit
breaker Moeller
PKZM0-16
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
AQ267037727118en-000101 / 130R0300
Specifications
rms
Maximum trip
level [A]
16
25
25
25
25
63
100
50
100
160

Advertisement