HIPERFACE
EnDat
6.2.3 VLT
®
Resolver Option MCB 103
The MCB 103 option enables connection of a resolver to
provide speed feedback from the motor.
Primary voltage: 2–8 V
Primary frequency: 2.0–15 kHz
Primary maximum current: 50 mA rms
Secondary input voltage: 4 V
Spring-loaded connection
6.2.4 VLT
®
Relay Card MCB 105
®
The VLT
Relay Card MCB 105 extends relay functions with
3 more relay outputs.
Protects control cable connection.
Spring-loaded control wire connection.
Maximum switch rate (rated load/minimum load)
6 minutes
-1
/20 s
-1
.
Maximum terminal load
AC-1 resistive load: 240 V AC, 2 A.
6.2.5 VLT
®
Safe PLC Interface Option
MCB 108
The MCB 108 option provides a safety input based on a
single-pole 24 V DC input. For most applications, this input
provides a way to implement safety in a cost-effective way.
For applications that work with more advanced products
like Safety PLC and light curtains, the fail-safe PLC interface
enables the connection of a 2-wire safety link. The PLC
Interface allows the fail-safe PLC to interrupt on the plus or
the minus link without interfering with the sense signal of
the fail-safe PLC.
6.2.6 VLT
®
PTC Thermistor Card MCB 112
The MCB 112 option provides extra motor monitoring
compared to the built-in ETR function and thermistor
terminal.
Protects the motor from overheating.
ATEX-approved for use with Ex-d and Ex-e motors
(EX-e only FC 302).
Uses Safe Torque Off function, which is approved
in accordance with SIL 2 IEC 61508.
MG38C202
Design Guide
rms
rms
Danfoss A/S © 01/2018 All rights reserved.
6.2.7 VLT
®
Sensor Input Option MCB 114
®
The VLT
Sensor Input Option MCB 114 protects the motor
from being overheated by monitoring the temperature of
motor bearings and windings.
3 self-detecting sensor inputs for 2 or 3-wire
PT100/PT1000 sensors.
1 extra analog input 4–20 mA.
6.2.8 VLT
®
Safety Option MCB 150 and
MCB 151
MCB 150 and MCB 151 options expand the Safe Torque Off
functions, which are integrated in a standard VLT
AutomationDrive FC 302. Use the Safe Stop 1 (SS1)
function to perform a controlled stop before removing
torque. Use the Safety-Limited Speed (SLS) function to
monitor whether a specified speed is exceeded.
These options can be used up to PL d according to ISO
13849-1 and SIL 2 according to IEC 61508.
Extra standard-compliant safety functions.
Replacement of external safety equipment.
Reduced space requirements.
2 safe programmable inputs.
1 safe output (for T37).
Easier machine certification.
Drive can be powered continuously.
Safe LCP copy.
Dynamic commissioning report.
TTL (MCB 150) or HTL (MCB 151) encoder as
speed feedback.
6.2.9 VLT
®
Safety Option MCB 152
The MCB 152 option activates Safe Torque Off via the
®
PROFIsafe fieldbus with VLT
option. It improves flexibility by connecting safety devices
within a plant.
The safety functions of the MCB 152 are implemented
according to EN IEC 61800-5-2. The MCB 152 supports
PROFIsafe functionality to activate integrated safety
®
functions of the VLT
AutomationDrive FC 302 from any
PROFIsafe host, up to Safety Integrity Level SIL 2 according
to EN IEC 61508 and EN IEC 62061, and Performance Level
PL d, Category 3 according to EN ISO 13849-1.
PROFIsafe device (with MCA 120).
Replacement of external safety equipment.
®
PROFINET MCA 120 fieldbus
33