Danfoss VLT AutomationDrive FC 302 Design Manual page 45

90–710 kw, enclosure sizes d and e
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Specifications
®
VLT
AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s,
normal overload=110% current during 60 s)
Typical shaft output at 525 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 525 V) [A]
Intermittent (60 s overload) (at 525 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 525 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 525 V) [A]
Continuous (at 575/690 V) [A]
Maximum number and size of cables per phase (E2h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Brake or regen [mm
2
(AWG)]
Maximum number and size of cables per phase (E4h)
- Mains and motor [mm
2
(AWG)]
2
- Brake [mm
(AWG)]
- Load share or regen [mm
2
(AWG)]
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
Efficiency
3)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
Table 7.8 Electrical Data for Enclosures E1h–E4h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
MG38C202
Design Guide
N560
HO
450
600
560
E2h/E4h
596
894
570
855
568
568
681
574
549
6x240 (6x500 mcm)
2
(AWG)]
5x240 (5x500 mcm)
2
(AWG)]
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
1)
8069
2), 3)
7848
2), 3)
0.98
0–500
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
Danfoss A/S © 01/2018 All rights reserved.
N630
NO
HO
500
500
650
650
630
630
E2h/E4h
630
659
693
989
630
630
693
945
600
628
627
627
753
753
607
635
607
607
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
1200
9208
8543
8921
8363
0.98
0–500
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
± 15% (tolerance relates to variety in voltage and cable conditions). These
N710
NO
HO
NO
560
560
670
750
750
950
710
710
800
E2h/E4h
763
763
889
839
1145
978
730
730
850
803
1095
935
727
727
847
727
727
847
872
872
1016
735
735
857
704
704
819
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
1200
10346
10319
12723
10066
10060
12321
0.98
0–500
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
7
7
43