Danfoss VLT AutomationDrive FC 302 Design Manual page 188

90–710 kw, enclosure sizes d and e
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Application Examples
Speed
Start/Stop (18)
Illustration 12.2 Start/Stop with Safe Torque Off
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
12
12
Table 12.6 Wiring Configuration for Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Illustration 12.3 Latched Start/Stop Inverse
186
VLT® AutomationDrive FC 302
Parameters
Function
Setting
Parameter 5-10 T
[9] Latched
erminal 18
Start
Digital Input
Parameter 5-12 T
[6] Stop
erminal 27
Inverse
Digital Input
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
Danfoss A/S © 01/2018 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
29
D IN
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 12.7 Wiring Configuration for Start/Stop with Reversing
and 4 Preset Speeds
Parameters
Function
Setting
Parameter 5-10 T
[8] Start
erminal 18
Digital Input
Parameter 5-11 T
[10]
erminal 19
Reversing*
Digital Input
Parameter 5-12 T
[0] No
erminal 27
operation
Digital Input
Parameter 5-14 T
[16] Preset ref
erminal 32
bit 0
Digital Input
Parameter 5-15 T
[17] Preset ref
erminal 33
bit 1
Digital Input
Parameter 3-10 P
reset Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
*=Default value
Notes/comments:
MG38C202