Control Panel Installation

4.2 AC Connection

At installation, connect the AC terminals to the power source as shown in Figure 4.3. It may be necessary for a professional electrician to
make this connection.
WARNING:
RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF
!
POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING
AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
AC power for the IFP-75 is rated at 120VAC, 60Hz, 1.5A.
AC power for the IFP-75HV is rated at 240VAC, 50/60Hz, 1A.
26
PRI: 120V, 60Hz
240V, 50/60Hz,
BLK-WHT
SEC: 36V, 85VA
YEL-YEL
120/240V
Figure 4.3 120/240V Power Connection
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
supervised
To AC
ground
AC Connection