Release Control Panel Main Features - Honeywell NOTIFIER RP1r User Manual

Extinguishing control panel
Table of Contents

Advertisement

1.6 Release control panel main features

Compact control panel with double microprocessor.
Supply Rating: 90-264Vac 50/60Hz. Total power: 65W (2,4A a 27Vcc). Maximum current
supplied by Release control panel: 2,4Amp.
2 monitored sounder outputs (2 x 250mA)
2 auxiliary power supply outputs 2 x 250mA (non-resettable and resettable).
2 release circuits. Maximum current of each release circuit: 1Amp. (Remember that the max.
current that the control panel can supply is 2,4Amp).
Control panel quiescent current: 125mA.
Battery charge current: 300mA maximum (7A/h batteries).
Battery fuse: F4L 250V (4Amp).
All the outputs have electronic fuses for short circuits protection.
Panel sealing: IP30.
History log of 450 events to be displayed by PK-RP1r.
Climatic classification: Class A, indoor. Operating temperature: -5ºC to +40ºC. Humidity: 95%
max. R.H.
2 conventional detection zones for detectors and 1 conventional detection zone for detectors or
manual release.
Extinguishing abort and hold devices.
Programmable sounders delay (rS) before sounders activation from 1 to 10 min.
Sounder delays override by keyboard, call point alarm or 2 zones in alarm.
Input circuits for flow and low pressure, open door control and mechanical release disablement.
2 release circuits. The second release circuit can be used for preactivation, independently from
zone prealarm/alarm and it also activates with Release Output 1 by default.
Countdown timer indicating the seconds left to release.
36 indicator leds for quick identification of events.
Relays:
General alarm (Pre-activation)
o
Extinguishing process activated (coincidence)
o
Evacuate
o
Extinguishing release in process
o
Release circuit fault
o
General fault
o
Flow pressure switch
o
Status:
o
Open collector output to signal release in:
Hold mode
o
Abort mode
o
Digital input for remote actions configurable as: system reset, Evacuate, silence or delay on/off.
Plug-in terminals for all connections.
Software to display the system status in a PC.
Designed in compliance with EN54-2, EN54-4/A2:2006 and EN12094/1:2003.
Dimensions (mm): 379 (width) x 356 (height) x 95 (depth).
22 June 2011
Manual
Automatic
Release disabled.
Extinguishing control panel. User manual
4

Advertisement