2: Point Programming For The Internal Or External Power Module - Honeywell SILENT KNIGHT 6700 Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Point
Type
Function
Selection
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
DETECT SW
SWITCH
TAMPER
MAN REL
ILOCK
CO DETECT SW
CO SUPERVISORY
DETECT SW
STATUS PT
TROUBLE_MON
OUTPUT PT
AUX CONST
NOTIF
AUX RESET
AUX DOOR
OUTPUT PT
AUX RESET
RELAY
AUX DOOR
W-Gateway
W-SWITCH
Same as SWITCH
W-Relay
Same as Relay
8.5.2 Point Programming for the Internal or External Power Module
To program for an internal or external power module points, follow these steps:
1.
Login to the panel.
2.
Select 7 to access the Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrows to select the desired module. Press ENTER. Refer to Section 7.5 for the available choices.
5.
Enter the number of the circuit or point you want to edit. Refer to the table below for available selections.
6.
Press ENTER.
7.
To select the Type, press the up or down arrows, then, press ENTER.
8.
To select the Function, press the up or down arrows, then, press ENTER.
9.
To select the Group, press the up or down arrows, then, press ENTER.
10. To edit the Point Name, press the right arrow to skip Point Name Edit. See Section 8.5.
11. Repeat steps 1 through 10 for all circuits.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Latching
Option
Latching
Use these switch types if you want to monitor special zone-level conditions.
Non Latching
Latching
Non Latching
Latching
Use these switch types if you want to monitor special system-wide conditions.
Non Latching
Latching
Non Latching
Used to monitor conventional 4-wire detectors, a contact closure will generate a detector
alarm event.
Latching
Performs identically to a supervisory switch, but will be indicated as a tamper switch on the
LCD annunciator.
Non Latching
Manual release switch, typically a pull station.
Interlock release switch input.
CO Detector Switch
CO Supervisory Detector Switch
Status Point Switch
Use this switch type to monitor trouble from external devices. Trouble monitors are used in
HVAC operations.
Select Group
Output Point, a general use notification type. Use for driving standard notification
appliances.
Use constant power for applications that require a constant auxiliary power source. Power
is always present at Constant circuits.
Use for auxiliary power, resettable applications. See "Resettable Power" on page 48 to
learn how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using an
auxiliary power supply for door holders, you would use this option. See "Door Holder
Power" on page 47 to learn how this option operates.
Select Group
Output Point, a general use relay type. Use for applications requiring a relay, such as
elevator recall.
Use for auxiliary power, resettable applications. See "Resettable Power" on page 48 to
learn how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using an
auxiliary power supply for door holders, you would use this option. See "Door Holder
Power" on page 47 for a description of how this option operates.
Wireless Gateway
Table 8.3 Point Programming for Internal SLC Module (Continued)
Comments
Programming
81