3: Point Programming For Internal Or External Power Module (5895Xl) - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Programming
Type Selection
Detector
W-Gateway
W-SWITCH
W-Relay
8.5.3 Point Programming For Internal or External Power Module (5895XL)
To program for an internal or external power module points:
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices, then press ENTER.
5.
Enter the number of the circuit or point you wish to edit, then press ENTER.
6.
Select the type by pressing the up or down arrow key, then press ENTER.
7.
Select the function by pressing the up or down arrow key, then press ENTER.
8.
If the point supports latching press the up or down arrow key to select latching or non-latching, then press ENTER.
9.
Select the zone or group by pressing the up or down arrow key, then press ENTER.
10. If the point supports not being supervised, press the up or down arrow key to select supervised or non-supervised, then press ENTER.
11. Press ENTER to edit point name. See Appendix A for help with editing text. Or, Press right arrow key to skip point name edit.
12. Repeat Steps 1 through 11 for all circuits.
Choices
Enter Point
Select Type
100
Function
Latching Option
2-Wire Smoke
Same as SWITCH
Same as Relay
Table 8.5 Programming Options for 6815 Modules (Continued)
Function Selections
Type Selections
UNUSED
B NOTIF
NOTIF OUTPUT
CONTROL CIRCUIT
A NOTIF
Same as B NOTIF
AUX_PWR
CONSTANT
AUX RESET
AUX DOOR
AUX SYNC
B SWITCH
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
EVS INPUT
EVS TAMPER
EVS SUPERVISORY
A SWITCH
Same as B SWITCH
Table 8.6 Menu Choices for Internal/External Power Module
Wireless Gateway
When a wireless relay is in use, module device count must be limited to 109
modules per loop. This includes wired and wireless modules that are on the
same loop. The module address must be within 1-109.
for each Type
User also has Supervised/Unsupervised option
Constant auxiliary power
Resettable auxiliary power
Door holder auxiliary power
Refer to comments column of
Table 8.5 for description of these options.
Latch or Non-latching feature only appears for WATERFLOW, FIRE
SUPERVISORY, FIRE TAMPER, ZONE AUX1, ZONE AUX2,
SYSTEM AUX1, SYSTEM AUX2, ECS INPUT, ECS TAMPER, and
ECS SUPERVISORY.
User also has EVS Event Number 1-8 option for EVS INPUT.Only
available when a EVS-VCM is installed in the system.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022